Date |
Text |
2005-07-25 00:00:00 | ************ UNSAT ************** |
| |
| 1)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| PER 210.52 FOR 2' OF WALL SPACE. MAST |
| BEDRM, CAFE, |
| |
| 2)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| PLEASE SEE MISSING SD'S INSIDE/OUTSIDE |
| MASTER BEDRM. |
| |
| 3)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS |
| A DEDICATED CIRCUIT FOR A WHIRLPOOL GFI, |
| HOWEVER THIS RECEPT COULD NOT BE LOCATED |
| ON PLANS?? |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE "GOLF CART CIRCUIT |
| SHOWN ON PANEL SCHEDULE ALSO, WHICH |
| COULD NOT BE LOCATED ON PLANS. |
| 215.5 |
| |
| 5)NOTE; PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM MAINS TO SUB |
| PANELS. |
| 250.110,250.24, SIZE PER 250.122 |
| |
| 6)NOTE: PLEASE SEE MIN AIC RATING FROM |
| CALCULATIONS ARE OVER MIN AIC RATINGS |
| SHOWN ON PLANS. |
| AIC RATINGS SHALL BE OVER AVAILABLE |
| FAULT CURRENT, RATINGS MAY NOT BE LESS. |
| 110.9, 215.5 |
| |
| 7)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| ON POOL PANEL @125%. PLEASE SEEE THIS |
| WILL AFFECT FEEDER FROM PANEL "B" TO |
| POOL PANEL. LOAD IS ALREADY SHOWN AT |
| 59A'S. |
| 215.3,230.42,680.9 ETC. |
| |
| 8)NOTE: PLEASE LIST ALL THE REQUIRED ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE. PLEASE SEE ALL ARC FAULT |
| PROTECTION SHALL BE LISTED PER 2002 NEC |
| 210.12 |
| |
| 9)NOTE: PLEASE SEE "WHITE-OUT" ON PLANS |
| IS NOT PERMITTED TO PLANS SIGNED AND |
| SEALED BY AN ARCHITEC. |
| FS 481.221 |
| |
| 10)NOTE: PLEASE CLARIFY SIGNED PLANS. |
| PLEASE SEEE PLANS APPEAR TO BE SIGNED |
| WITH INITIALS? IF INDEED LEGAL SIGNATURE |
| FOR ARCHITECT, PLEASE PROVIDE A LETTER |
| TO VERIFY LEGAL SIGNATURE. THIS LETTER |
| SHALL BE SIGNED, DATED AND SEALED BY |
| ARCHITECT. THE LETTER SHOULD ALSO BE |
| NOTORIZED UNDER FS 117. |
| THIS LTR WILL BE PLACED IN SIGNATURE |
| FILE FOR ANY FUTURE VERIFICATION. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE COPY OF OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2005-07-22 00:00:00 | IN ELEC FOR REVIEW |