Plan Review Notes
Plan Review Notes For Permit 05070484
Permit Number 05070484
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-18 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE NOTE THAT ANY CHANGES MADE TO THE
 DRAWING MUST BE MADE BY THE DESIGN
 PROFESSIONAL WHOS NAME IS ON THE PLAN.
 ALSO IT MUST BE SIGNED AND SEALED BY
 SAME. SEE 481 FS.
  
 THE ELECTRICAL CONTRACTOR MAY DRAW HIS
 OWN PLANS FOR THIS WORK UNDER THE
 EXEMPTIONS IN 481. HE WOULD BE REQUIRED
 TO PRINT AND SIGN HIS NAME ON THE
 DOCUMENTS PER 140.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  