Plan Review Notes
Plan Review Notes For Permit 05070440
Permit Number 05070440
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHTS A-1 & A-3, SHOW THE CLEAR FLOOR
 SPACE FOR THE W/C'S, LAVS, LOUNGE SINK,
 AND WATER COOLER:
 A. 11-4.15.5
 B. 11-4.16.2
 C. 11-4.19.3
 D. 11-4.24.5
 AND SHOW THE FOLLOWING FOR THE LAVS:
 E. 11-4.19.5
 AND SHOW THE FOLLOWING FOR THE LOUNGE
 SINK:
 F. 11-4.24.3 KNEE CLEARANCE (27")
 G. 11-4.24.4 SINK DEPTH
 H. 11-4.24.6 EXPOSED PIPES & SURFACES
 I. 11-4.24.7 FAUCETS
 2. SHT P-2 DOMESTIC WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE SHOWN AT
 THE WASH MACHINE AND THE ICE MAKER PER
 SECTION 604.9 AND SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" PER
 PDI-WH 201. (NOT IN THE CEILING).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]