2005-07-20 00:00:00 | DENIED |
| |
| 1)705.7.1 JOINTS INSTALLED IN OR |
| BE- TWEEN FIRE RESISTANT WALLS, FIRE |
| RESIS- TANT FLOORS OR FLOOR/ CEILING |
| ASSEMBLIES AND FIRE RESISTANT ROOFS OR |
| ROOF/ CEIL- ING ASSEMBLIES SHALL BE |
| PROTECTED BY AN APPROVED FIRE RESISTANT |
| JOINT SYSTEM DESIGNED TO RESIST THE |
| PASSAGE OF FIRE FOR A PERIOD NOT LESS |
| THAN THE RE- QUIRED FIRE RESISTANCE |
| RATING OF THE WALL, FLOOR OR FLOOR IN OR |
| BETWEEN WHICH IT IS INSTALLED. SHOW |
| COMPLIANCE AT DETAIL 7 ON A4. |
| |
| 2) 1204.2 SURROUNDING MATERIALS; |
| THE WALLS & FLOORS OF ALL PUBLIC REST- |
| ROOMS SHALL BE LINED WITH NONABSORBANT |
| MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| FLOOR. |
| |
| 3) 704.2.1.4 CORRIDOR PARTITIONS, |
| SMOKE STOP PARTITIONS, HORIZONTAL EXIT |
| PART- ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 4)TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY. |
| |
| 5) PROVIDE A DETAIL OF THE EXISTING ONE |
| HOUR FIRE RATED COLUMNS. SPECIFY THE |
| MATERIAL AND REQUIRED THICKNESS OF THE |
| SPRAYED ON FIREPROOFING. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |