Plan Review Notes
Plan Review Notes For Permit 05070374
Permit Number 05070374
Review Stop M
Sequence Number 3
Notes
Date Text
2007-03-07 15:40:25MECHANICAL REVISION PAGE M1.1 AND M1.2.
 *** DENIED ***
 1)PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED
 CONDENSER STANDS, SEE FS 553.842(1) AND FAC
 9B-72.010(31)(G).
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 2) 14" SUPPLY AND RETURN AIR DUCT FROM A/C SYSTEM 2 IS
 TO SMALL. A 14" DUCT AT 1200 CFM'S IS A VELOCITY OF
 1100 FPM, MANUAL J CALCULATIONS STATE THE MAXIMUM
 VELOCITY IS 900 FPM, ALSO THE 12" SUPPLY AIR DUCT TO
 THE MIXING BOX. PLEASE CORRECT.
  
 3) PLEASE RE-DO MANUAL J CALCULATIONS AS A THREE TON
 A/C SYSTEM WOULD BE A LOT OF A/C FOR JUST 563 SQUARE
 FEET.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.