Date |
Text |
2007-02-26 11:13:55 | |
| |
| REVISION DENIED/INCOMPLETE INFORMATION |
| |
| 1} THERE IS A DELTA '2' INDICATING THE REVISION, BUT |
| NOT MARKED ON THE PLAN. PLEASE INDICATE BY CLOUDING OR |
| SOME OTHER MEANS WHERE THESE CHANGES ARE. |
| |
| 2} THE WIRING IN THE "OFFICE" WAS DELETED FROM THIS |
| PLAN. IF THESE SHEETS ARE REVISING PREVIOUS PLANS, ALL |
| WORK ORIGINALLY SHOWN MUST BE ON THE REVISED SHEET AS |
| IT REPLACES THE PREVIOUS SHEET. |
| |
| 3} THERE ARE SOME STRUCTURAL CHANGES ON THIS PLAN, BUT |
| NO STRUCTURAL REVISIONS HAVE BEEN SUBMITTED. ANY |
| ELECTRICAL CHANGES AFFECTED BY STRUCTURAL CHANGES MUST |
| BE SUBMITTED AT THE SAME TIME, OR AFTER THE STRUCTURAL |
| CHANGES HAVE BEEN PREVIOUSLY REVIEWED. |
| |
| 4} AS PREVIOUSLY NOTED ON THE PLAN, A GFI IS REQUIRED |
| FOR THE WHIRLPOOL TUB PER 680.71. THIS MAY BE AT THE |
| PANEL IN THE FORM OF A BREAKER OR A RECEPTACLE, BUT |
| MUST BE SHOWN ON THE PLAN. |
| |
| 5} SHEET E1.2 EXISTING BATH INDICATES BY NOTE |
| COMPLIANCE WITH ARTICLE 3401.7.1.2, REVIEW REQUIRES |
| THAT THE RECEPTACLE REQUIRED TO COMPLY BE LOCATED ON |
| THE PLAN FOR COMPLIANCE WITH 210.52(D) AS WELL AS |
| 210.8(A)(1). |
| |
| 6} THE #2 THHN EQUIPMENT GROUND BETWEEN THE METER AND |
| DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| FROM THE FIRST MEANS OF DISCONNECT. 250.6. SHEET E2.1, |
| RISER DIAGRAM. |
| |
| 7} THE FEEDERS TO THE EXISTING PANEL (3/0) AND THE NEW |
| PANEL "A" (4/0) IN THE MDP, DO NOT CORRELATE WITH THE |
| "3-2/0 " FEEDERS ON THE RISER DIAGRAM. |
| |
| 8} THREE PANELS HAVE BEEN REMOVED FROM THE PERMITTED |
| PLANS. INDICATE THE ORIGINAL LOCATIONS OF THESE PANELS |
| AND THE LOCATION OF THE JUNCTION BOXES THAT MUST HAVE |
| REPLACED THESE PANELS.215.5. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |