Plan Review Notes For Permit 05070374 |
Permit Number |
05070374 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-26 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SEE THE FEEDER CONDUCTOR SIZES | | TO THE PANELS FROM MDP ARE TOO LARGE. | | THIS IS NOT A VIOLATION BUT MUST BE | | INSTALLED IF THEY REMAIN ON THE PLAN, OR | | A REVISION TO THE PLAN WILL BE REQUIRED. | | ALSO SOO THE 3/0 & 4/0S WILL NOT FIT ON | | 100 AMP BREAKERS. | | | | 2} PANEL "B" IS 200 AMP ON THE SCHEDULE | | , 100 AMP IN THE MDP.PLEASE CORRELATE. | | | | 3} BOTH AC UNITS ARE MARKED #1 ON THE | | RISER. SEE PANEL "B" CIRCUITS 9,10,11 & | | 12. | | | | 4} PLEASE VERIFY BOND WIRE SIZES, SEE | | COMMENT #1. | | | | 5} PLEASE VERIFY THE SIZE AND NUMBER OF | | THE SERVICE CONDUCTORS FROM THE METER TO | | THE MDP. INDICATE CONDUIT(S) SIZES AND | | NUMBER OF CONDUCTORS IN EACH. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|