Plan Review Notes
Plan Review Notes For Permit 05070374
Permit Number 05070374
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THE FEEDER CONDUCTOR SIZES
 TO THE PANELS FROM MDP ARE TOO LARGE.
 THIS IS NOT A VIOLATION BUT MUST BE
 INSTALLED IF THEY REMAIN ON THE PLAN, OR
 A REVISION TO THE PLAN WILL BE REQUIRED.
 ALSO SOO THE 3/0 & 4/0S WILL NOT FIT ON
 100 AMP BREAKERS.
  
 2} PANEL "B" IS 200 AMP ON THE SCHEDULE
 , 100 AMP IN THE MDP.PLEASE CORRELATE.
  
 3} BOTH AC UNITS ARE MARKED #1 ON THE
 RISER. SEE PANEL "B" CIRCUITS 9,10,11 &
 12.
  
 4} PLEASE VERIFY BOND WIRE SIZES, SEE
 COMMENT #1.
  
 5} PLEASE VERIFY THE SIZE AND NUMBER OF
 THE SERVICE CONDUCTORS FROM THE METER TO
 THE MDP. INDICATE CONDUIT(S) SIZES AND
 NUMBER OF CONDUCTORS IN EACH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  