Date Text
2005-09-20 00:00:00RISER DIAGRAM SHOWS 2/0 CONDUCTORS OR
 THE 200A SERVICE THIS IS ONLY FOR A
 RESIDENTIAL DWELLING.WIRE IS TOO SMALL
 SHOULD BE 3/0.