Plan Review Notes
Plan Review Notes For Permit 05070334
Permit Number 05070334
Review Stop E
Sequence Number 3
Notes
Date Text
2007-08-20 14:43:59*** DENIED ***
  
  
 1) NOTE: PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE COVER SHEET REFERENCING PLANS DESIGN
 STILL STATES THE 2004 FBC WHEN THIS SHOULD REFLECT THE
 2001 FBC.
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO THE CORRECT LICENSE INFORMATION AND TITLE
 BLOCK INFORMATION TO BE ON PLANS. THIS IS INCLUSIVE OF
 MEP SHEETS.
 PLEASE SEE THE ATTACHED PRINT OUT DATED THE SAME DATE
 OF THIS REVIEW WHICH SHOWS THE PRINT OUT FOR
 ENGINEERING FIRM FROM THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 PLEASE SEE THE FIRM NAME AS LISTED ON THE STATE WEBSITE
 DOES NOT COORDINATE WITH THE PLANS.
 PLEASE KNOW IT IS OUR UNDERSTANDING FROM THE DBPR THAT
 THIS INFORMATION NEEDS TO MATCH. PLEASE HAVE STATE
 UPDATE WEBSITE IF INDEED THIS INFORMATION ON TITLE
 BLOCKS IS CORRECT OR UPDATE TITLE BLOCKS TO MATCH
 LICENSURE WITH THE STATE.
 PLEASE KNOW A LETTER FROM THE DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION STATING THIS INFORMATION
 DOES NOT NEED TO MATCH IS ACCEPTABLE. MUST BE ORIGINAL
 AND NOTARIZED FROM THE STATE.
 FAC 61G15-23.002, FS 471.023, FS 117.05
  
 3) NOTE: PLEASE SEE NO RESPONSE FROM THE DESIGN
 PROFESSIONAL WAS SUBMITTED WITH RESPECT TO PREVIOUS
 COMMENT NUMBER 7. THE PLANS WERE REVISED HOWEVER WITH A
 NOTE WHICH STATES THE SERVICE MEETS 230.2 EXCEPTION #7.
 PLEASE CLARIFY THIS AS UPON REVIEW OF THE 1999, 2002
 AND 2005 NEC COULD NOT ANY *EXCEPTION #7* AS STATED.
 PLEASE VERIFY HOW THE ADDITIONAL SERVICE MEETS 230.2.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  