2007-06-26 17:09:23 | |
| |
| *** UNSAT *** |
| |
| REVISIONS: |
| |
| 1) NOTE: PLEASE SEE THE REVISIONS ARE NOW COMING IN |
| DESIGNED AND SHOWING SEVERAL CODES WHICH ARE CURRENTLY |
| IN EFFECT. PLEASE KNOW THE PERMITTED WORK FOR THIS |
| BUILDING WAS UNDER PREVIOUS CODES AS STATED BELOW. |
| ** PLEASE KNOW IF THE DESIGNS WERE UNDER THE 2004 FBC |
| THERE WAS NO DESIGNS TO FBC CHAPTER 13. |
| |
| THE FOLLOWING CODES WERE APPLICABLE WHEN THIS PERMIT |
| WAS APPLIED. |
| 2001 FBC |
| 1999 NFPA-70 (NEC). |
| 1997 NFPA-101 LIFE SAFETY CODE |
| 1999 NFPA-72 |
| |
| ** PLEASE SEE ANY COMMENTS FROM OTHER TRADE WHICH ALSO |
| MAY REQUEST CERTAIN CODE CHANGES. |
| |
| 2) NOTE: NEW DESIGNERS OF RECORD: |
| PLEASE SEE THE LICENSE NUMBER AS STATED AND SEALED ON |
| PLANS IS SHOWN ON THE STATE WEBSITE FROM THE DEPARTMENT |
| OF BUSINESS AND PROFESSIONAL REGULATION AS * |
| DELINQUENT*. PLEASE SEE ATTACHED PRINT OUT FROM DBPR. |
| FS 481. |
| |
| 3) NOTE: NEW ELECTRICAL DESIGNER/ENGINEER OF RECORD. |
| PLEASE SEE THE SEAL WHICH IS BEING USED IS NO LONGER |
| VALID WITH THE STATE OF FLORIDA. PLEASE SEE RULING |
| UNDER THE FLORIDA ADMINISTRATIVE CODE 61G15-23.001 IN |
| FEBRUARY 04 WHICH REQUIRED ALL SEALS FOR ENGINEERS TO |
| CHANGE THE WORDING ON THE SEAL FROM *CERTIFICATE* TO |
| THE WORDING OF *LICENSE*. AN EXTENSION WAS GIVEN TO THE |
| DATE OF DECEMBER 31, 2005 HOWEVER ALL SEALED DOCUMENTS |
| AFTER THAT DATE MUST HAVE NEW SEAL. PLEASE OBTAIN NEW |
| SEAL FOR SAID DOCUMENTS. |
| FS 471.025 |
| |
| 4) NOTE: PLEASE SEE MISSING INFORMATION FROM TITLE |
| BLOCKS FOR ENGINEERING FIRM AS REQUIRED UNDER FAC |
| 61G15-23.002 AND FLORIDA STATUTES 471.023. |
| PLEASE SEE THE MISSING *CERTIFICATE OF AUTHORIZATION |
| NUMBER* ALSO KNOWN AS THE ENGINEERING BUSINESS NUMBER |
| OR FIRM LICENSE NUMBER. |
| ** PLEASE SEE THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| TRADE(S). |
| |
| 5) NOTE: PLEASE SEE THE PLANS NEED TO SHOW ALL |
| LOCATIONS AND ALL MINIMUM LEVELS FOR HORNS, STROBES AND |
| HORN/STROBE DEVICES. |
| PLEASE SEE 2001 FBC 11-4.28.1,.2, AND .3(4). |
| |
| 6) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS PER |
| 2001 FBC CHAPTER 13. |
| A) PLEASE SEE THAT THESE ARE REQUIRED TO BE SIGNED, |
| DATED, AND SEALED BY THE DESIGNER OF RECORD ALONG WITH |
| SIGNATURE FROM OWNER AGENT. FS 481.221/ 471.025, FAC |
| 61G15-23.002, 61G1-16.004 |
| B) PLEASE SEE PLANS ARE MISSING THE FIXTURE LEGEND FOR |
| LIGHTING FIXTURES. PLEASE PROVIDE ALL INFORMATION FOR |
| THESE AND BE SURE TO CORRELATE WITH REVISED ENERGY |
| CALCULATIONS. |
| |
| 7) NOTE: PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN |
| COMPLETELY REVISED WITH SEVERAL ITEMS INCLUDING NOW |
| SHOWING A NEW SERVICE WHICH DOES NOT MEET THE |
| EXCEPTIONS OF 230.2. |
| PLEASE SEE THE RISER DIAGRAM ITSELF IS NOT SHOWN AS |
| CODE COMPLIANT. |
| PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ARE SHOWN |
| FOR THE FPL TRANSFORMER UNDERGROUND AND THEN THERE ARE |
| THREE SETS OF TAPS FROM THE SAME UNDERGROUND???? |
| PLEASE SEE ONE TAP FOR A NEW A/C MAIN, A NEW FIRE PUMP |
| MAIN, AND THE MAIN FOR THE BUILDING ELECTRICAL |
| SERVICE. |
| PLEASE SUBMIT A REVISED DIAGRAM WHICH INDICATES CODE |
| COMPLIANCE WITH THE NEC. |
| 215.5,240.21,230.2,230.70,230.71 ETC. |
| THE TAPS AS SHOWN ON RISER ARE NOT CLEAR AND ARE NOT |
| PERMITTED. |
| |
| 8) NOTE: PLEASE SEE RISER SHOWS AND NEW FIRE SPRINKLER |
| MAIN WHICH CAN ONLY BE ASSUMED AS A FIRE PUMP MAINS |
| HOWEVER THE PLANS DO NOT INDICATE ANY INFORMATION FOR |
| THIS. |
| PLEASE SEE 230.2, 230.70, 695.4 AND NFPA-20 FOR ALL |
| INFORMATION NEEDED. |
| PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THE |
| FIRE PUMP AND FIRE PUMP CONTROLLER. |
| PLEASE INDICATE THE LOCATION AND INFORMATION ON PLANS |
| AS THESE COULD NOT BE LOCATED ON PLANS. |
| ** PLEASE KNOW AS NO INFORMATION WAS SHOWN OR |
| SUBMITTED, A REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE |
| AT THIS TIME. |
| PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT. |
| |
| 9) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE |
| EQUIPMENT AS REQUIRED PER 110.9 OF THE NEC. |
| |
| 10) NOTE: PLEASE SEE THE TOTAL OF THE CONNECTED LOAD |
| AMPS SEEMS TO BE A MISPRINT AS THIS SHOWS 110.5 AMPS. |
| FBC104.1.2 COORDINATION. |
| |
| 11) NOTE: PLEASE SEE THE AIC RATING WHICH IS BEING |
| SHOWN ON THE MDP AS 65K, JUST A NOTE AS EACH OF THE |
| BRANCH BREAKERS IN THIS MLO WILL BE REQUIRED TO BE 65K |
| RATED AS SHOWN. |
| |
| *** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |