Plan Review Notes
Plan Review Notes For Permit 05070334
Permit Number 05070334
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-26 17:09:23 
  
 *** UNSAT ***
  
 REVISIONS:
  
 1) NOTE: PLEASE SEE THE REVISIONS ARE NOW COMING IN
 DESIGNED AND SHOWING SEVERAL CODES WHICH ARE CURRENTLY
 IN EFFECT. PLEASE KNOW THE PERMITTED WORK FOR THIS
 BUILDING WAS UNDER PREVIOUS CODES AS STATED BELOW.
 ** PLEASE KNOW IF THE DESIGNS WERE UNDER THE 2004 FBC
 THERE WAS NO DESIGNS TO FBC CHAPTER 13.
  
 THE FOLLOWING CODES WERE APPLICABLE WHEN THIS PERMIT
 WAS APPLIED.
 2001 FBC
 1999 NFPA-70 (NEC).
 1997 NFPA-101 LIFE SAFETY CODE
 1999 NFPA-72
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADE WHICH ALSO
 MAY REQUEST CERTAIN CODE CHANGES.
  
 2) NOTE: NEW DESIGNERS OF RECORD:
 PLEASE SEE THE LICENSE NUMBER AS STATED AND SEALED ON
 PLANS IS SHOWN ON THE STATE WEBSITE FROM THE DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION AS *
 DELINQUENT*. PLEASE SEE ATTACHED PRINT OUT FROM DBPR.
 FS 481.
  
 3) NOTE: NEW ELECTRICAL DESIGNER/ENGINEER OF RECORD.
 PLEASE SEE THE SEAL WHICH IS BEING USED IS NO LONGER
 VALID WITH THE STATE OF FLORIDA. PLEASE SEE RULING
 UNDER THE FLORIDA ADMINISTRATIVE CODE 61G15-23.001 IN
 FEBRUARY 04 WHICH REQUIRED ALL SEALS FOR ENGINEERS TO
 CHANGE THE WORDING ON THE SEAL FROM *CERTIFICATE* TO
 THE WORDING OF *LICENSE*. AN EXTENSION WAS GIVEN TO THE
 DATE OF DECEMBER 31, 2005 HOWEVER ALL SEALED DOCUMENTS
 AFTER THAT DATE MUST HAVE NEW SEAL. PLEASE OBTAIN NEW
 SEAL FOR SAID DOCUMENTS.
 FS 471.025
  
 4) NOTE: PLEASE SEE MISSING INFORMATION FROM TITLE
 BLOCKS FOR ENGINEERING FIRM AS REQUIRED UNDER FAC
 61G15-23.002 AND FLORIDA STATUTES 471.023.
 PLEASE SEE THE MISSING *CERTIFICATE OF AUTHORIZATION
 NUMBER* ALSO KNOWN AS THE ENGINEERING BUSINESS NUMBER
 OR FIRM LICENSE NUMBER.
 ** PLEASE SEE THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 5) NOTE: PLEASE SEE THE PLANS NEED TO SHOW ALL
 LOCATIONS AND ALL MINIMUM LEVELS FOR HORNS, STROBES AND
 HORN/STROBE DEVICES.
 PLEASE SEE 2001 FBC 11-4.28.1,.2, AND .3(4).
  
 6) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS PER
 2001 FBC CHAPTER 13.
 A) PLEASE SEE THAT THESE ARE REQUIRED TO BE SIGNED,
 DATED, AND SEALED BY THE DESIGNER OF RECORD ALONG WITH
 SIGNATURE FROM OWNER AGENT. FS 481.221/ 471.025, FAC
 61G15-23.002, 61G1-16.004
 B) PLEASE SEE PLANS ARE MISSING THE FIXTURE LEGEND FOR
 LIGHTING FIXTURES. PLEASE PROVIDE ALL INFORMATION FOR
 THESE AND BE SURE TO CORRELATE WITH REVISED ENERGY
 CALCULATIONS.
  
 7) NOTE: PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN
 COMPLETELY REVISED WITH SEVERAL ITEMS INCLUDING NOW
 SHOWING A NEW SERVICE WHICH DOES NOT MEET THE
 EXCEPTIONS OF 230.2.
 PLEASE SEE THE RISER DIAGRAM ITSELF IS NOT SHOWN AS
 CODE COMPLIANT.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ARE SHOWN
 FOR THE FPL TRANSFORMER UNDERGROUND AND THEN THERE ARE
 THREE SETS OF TAPS FROM THE SAME UNDERGROUND????
 PLEASE SEE ONE TAP FOR A NEW A/C MAIN, A NEW FIRE PUMP
 MAIN, AND THE MAIN FOR THE BUILDING ELECTRICAL
 SERVICE.
 PLEASE SUBMIT A REVISED DIAGRAM WHICH INDICATES CODE
 COMPLIANCE WITH THE NEC.
 215.5,240.21,230.2,230.70,230.71 ETC.
 THE TAPS AS SHOWN ON RISER ARE NOT CLEAR AND ARE NOT
 PERMITTED.
  
 8) NOTE: PLEASE SEE RISER SHOWS AND NEW FIRE SPRINKLER
 MAIN WHICH CAN ONLY BE ASSUMED AS A FIRE PUMP MAINS
 HOWEVER THE PLANS DO NOT INDICATE ANY INFORMATION FOR
 THIS.
 PLEASE SEE 230.2, 230.70, 695.4 AND NFPA-20 FOR ALL
 INFORMATION NEEDED.
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THE
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE INDICATE THE LOCATION AND INFORMATION ON PLANS
 AS THESE COULD NOT BE LOCATED ON PLANS.
 ** PLEASE KNOW AS NO INFORMATION WAS SHOWN OR
 SUBMITTED, A REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
 PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT.
  
 9) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT AS REQUIRED PER 110.9 OF THE NEC.
  
 10) NOTE: PLEASE SEE THE TOTAL OF THE CONNECTED LOAD
 AMPS SEEMS TO BE A MISPRINT AS THIS SHOWS 110.5 AMPS.
 FBC104.1.2 COORDINATION.
  
 11) NOTE: PLEASE SEE THE AIC RATING WHICH IS BEING
 SHOWN ON THE MDP AS 65K, JUST A NOTE AS EACH OF THE
 BRANCH BREAKERS IN THIS MLO WILL BE REQUIRED TO BE 65K
 RATED AS SHOWN.
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]