Plan Review Notes
Plan Review Notes For Permit 05070334
Permit Number 05070334
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-28 10:38:28DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P1 ONE SHEET ON ONE SET IS NOT SIGNED, SEALED,
 DATED AS REQUIRED BYSECTION 104.2.2, FAC
 61G15-23.004(1)(2) & FS 471.025
  
 2. ALL ELECTRIC, MECHANICAL & PLUMBING SHEETS. THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF THE ENGINEERING BUSINESS. FAC 61G15-23.002(2)
 & FS 471.025.
  
 3. SHT P2 DELETE THE SANITARY BRANCH LINE DOWNSTREAM OF
 THE JANITOR SINK OR INDICATE THE USE FOR THIS LINE.
 (NOT SHOWN ON THE RISER DIAGRAM). SECTION 104.2.1.
  
 4. SHT P3 A VENT IS REQUIRED FOR THE WATER CLOSET NEXT
 TO WATER HEATER 1A. TABLE 906.1.
  
 5. SHT P4 DETAIL 1 SEE PREVIOUS COMMENT #4.
  
 6. SHT P4 DETAIL 3 SEE COMMENT #3.
  
 7. SHT P4 DETAIL 5 SHOW STUB-OUTS FOR THE URINALS.
 SECTION 104.2.1.
  
 8. SHT P6 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. IN THE GIRLS TOILET ROOM AT THE LAVS, 4
 W/C'S & FLOOR DRAIN, IN THE BOYS TOILET ROOM 1 URINAL
 IS MISSING. ALSO THE FLOOR PLAN IN THE BOYS SHOWER AT
 THE W/C AND THE GIRLS SHOWER THE W/C'S FACING EACH
 OTHER.--SINK-3, (NEXT TO W/H-3),IS MISSING
 BETWEEN TOILET ROOMS--THE WASTE ARMS FOR THE
 DRINKING FOUNTAINS AS INDICATED ARE "S" TRAPS AND SHALL
 STUB OUT STRAIGHT FROM THE FIXTURE BRANCH ARM.--
 SINK-4'S SHALL NOT DRAIN THRU THE WET VENT OF THE
 TOILET ROOMS. SECTION 909.1 (THESE ARE LOCATED AT THE
 WEST SIDE OF THE FLOOR PLAN AND NEAR THE GREAS
 INTERCEPTOR).--INDICATE 2-WAY CLEANOUTS ON EACH
 SIDE OF THE GREASE INTERCEPTOR. --REMOVE ALL TRAPS AT
 THE WATER CLOSETS ON THE RISER DIAGRAM. THE WATER
 CLOSETS HAVE INTEGRAL TRAPS AND DOUBLE TRAPING IS NOT
 APPROVED. SECTIONS 104.2.1, 1002.1. (SEE RED LINE
 CORRECTIONS ON ONE SET OF PLANS).
  
 9. SHT P8WATER HEATER DETAIL. SHOW THERMAL EXPANSION
 CONTROL AS REQUIRED IN SECTION 607.3.2.--FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS.
 DELETE FROM DETAIL REFERENCE. SECTIONS 802.3 & 802.3.2.
 --DIELECTRIC UNIONS ARE NOT ANAPPROVED FITTING FOR
 USE IN THEWATER SYSTEM. CHANGE REFERENCE TO
 "COUPLING".
  
 10. A LETTER INDICATING THAT AN ELECTRIC WATER HEATER
 HAS BEEN CHANGED TO A GAS WATER HEATER. A SEPARATE GAS
 PERMIT IS REQUIRED AND THE FOLLOWING INFORMATIO IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]