2007-06-28 10:38:28 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT P1 ONE SHEET ON ONE SET IS NOT SIGNED, SEALED, |
| DATED AS REQUIRED BYSECTION 104.2.2, FAC |
| 61G15-23.004(1)(2) & FS 471.025 |
| |
| 2. ALL ELECTRIC, MECHANICAL & PLUMBING SHEETS. THE |
| CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE TITLE |
| BLOCK OF THE ENGINEERING BUSINESS. FAC 61G15-23.002(2) |
| & FS 471.025. |
| |
| 3. SHT P2 DELETE THE SANITARY BRANCH LINE DOWNSTREAM OF |
| THE JANITOR SINK OR INDICATE THE USE FOR THIS LINE. |
| (NOT SHOWN ON THE RISER DIAGRAM). SECTION 104.2.1. |
| |
| 4. SHT P3 A VENT IS REQUIRED FOR THE WATER CLOSET NEXT |
| TO WATER HEATER 1A. TABLE 906.1. |
| |
| 5. SHT P4 DETAIL 1 SEE PREVIOUS COMMENT #4. |
| |
| 6. SHT P4 DETAIL 3 SEE COMMENT #3. |
| |
| 7. SHT P4 DETAIL 5 SHOW STUB-OUTS FOR THE URINALS. |
| SECTION 104.2.1. |
| |
| 8. SHT P6 SANITARY RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. IN THE GIRLS TOILET ROOM AT THE LAVS, 4 |
| W/C'S & FLOOR DRAIN, IN THE BOYS TOILET ROOM 1 URINAL |
| IS MISSING. ALSO THE FLOOR PLAN IN THE BOYS SHOWER AT |
| THE W/C AND THE GIRLS SHOWER THE W/C'S FACING EACH |
| OTHER.--SINK-3, (NEXT TO W/H-3),IS MISSING |
| BETWEEN TOILET ROOMS--THE WASTE ARMS FOR THE |
| DRINKING FOUNTAINS AS INDICATED ARE "S" TRAPS AND SHALL |
| STUB OUT STRAIGHT FROM THE FIXTURE BRANCH ARM.-- |
| SINK-4'S SHALL NOT DRAIN THRU THE WET VENT OF THE |
| TOILET ROOMS. SECTION 909.1 (THESE ARE LOCATED AT THE |
| WEST SIDE OF THE FLOOR PLAN AND NEAR THE GREAS |
| INTERCEPTOR).--INDICATE 2-WAY CLEANOUTS ON EACH |
| SIDE OF THE GREASE INTERCEPTOR. --REMOVE ALL TRAPS AT |
| THE WATER CLOSETS ON THE RISER DIAGRAM. THE WATER |
| CLOSETS HAVE INTEGRAL TRAPS AND DOUBLE TRAPING IS NOT |
| APPROVED. SECTIONS 104.2.1, 1002.1. (SEE RED LINE |
| CORRECTIONS ON ONE SET OF PLANS). |
| |
| 9. SHT P8WATER HEATER DETAIL. SHOW THERMAL EXPANSION |
| CONTROL AS REQUIRED IN SECTION 607.3.2.--FLOOR |
| DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. |
| DELETE FROM DETAIL REFERENCE. SECTIONS 802.3 & 802.3.2. |
| --DIELECTRIC UNIONS ARE NOT ANAPPROVED FITTING FOR |
| USE IN THEWATER SYSTEM. CHANGE REFERENCE TO |
| "COUPLING". |
| |
| 10. A LETTER INDICATING THAT AN ELECTRIC WATER HEATER |
| HAS BEEN CHANGED TO A GAS WATER HEATER. A SEPARATE GAS |
| PERMIT IS REQUIRED AND THE FOLLOWING INFORMATIO IS |
| REQUIRED FOR THE GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. TYPE OF GAS, (LP OR NATURAL). |
| |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. |
| |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| H. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| |
| I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| J. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| K. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |