Plan Review Notes For Permit 05070299 |
Permit Number |
05070299 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-01 00:00:00 | DENIED; | | 1. WATER HEATER REQUIRED.FBC PLUMBING | | SEC. 607.1. | | 2.AUTOMATIC CLOTHES WASHER CONNECTION | | REQUIRED PER TABLE 403.1 MIN. PLUMBING | | FACILITIES ONE AND TWO FAMILY DWELLINGS. | | 3.REMOVE DRAINAGE PIPE FROM DELETED | | BATHROOM TO WITHIN 2' OFF BUILDING DRAIN | | TO COMPLY WITH SEC.704.5.( ADD TO NOTES) | | 4. PLUMBING RISER DIAGRAM IS NOT TO CODE | | AND DOES NOT MATCH FLOOR PLAN. SEE SEC. | | 909.1. SEE RED LINE ONE SET OF PLANS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-695 |
|