2006-04-14 00:00:00PROVISO:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 PRIOR TO ROUGH INSPECTION:
  
 1.RTU-6 IS NOT INDICATED ON THE
 EQUIPMENT SCHEDULE.PLEASE PROVIDE
 INFORMATION REQUIRED FOR RTU-6 ON THE
 SCHEDULE INDICATE NEW OR EXISTING.
  
 2.RTU-6 - PROVIDE MISSING DUCT SIZE
 FOR THE RETURN AIR.
  
 3.RTU-1 - PROVIDE MISSING DUCT SIZE
 FOR THE RETURN AIR JUMPER.
  
 4.RESPONSE TO COMMENT #3 FROM PREVIOUS
 REVIEW INDICATES A 20 FT LADDER TO BE
 PROVIDED FOR PERMANENT MEANS OF ACCESS.
 PLEASE PROVIDE SUBMITTAL DATA FOR THE
 LADDER AS WELL AS A DETAIL FOR THE
 ATTACHMENT OF THE LADDER TO THE
 BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.