4 |
|
Notes |
Date |
Text |
2006-04-14 00:00:00 | PROVISO: | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | PRIOR TO ROUGH INSPECTION: | | | | 1.RTU-6 IS NOT INDICATED ON THE | | EQUIPMENT SCHEDULE.PLEASE PROVIDE | | INFORMATION REQUIRED FOR RTU-6 ON THE | | SCHEDULE INDICATE NEW OR EXISTING. | | | | 2.RTU-6 - PROVIDE MISSING DUCT SIZE | | FOR THE RETURN AIR. | | | | 3.RTU-1 - PROVIDE MISSING DUCT SIZE | | FOR THE RETURN AIR JUMPER. | | | | 4.RESPONSE TO COMMENT #3 FROM PREVIOUS | | REVIEW INDICATES A 20 FT LADDER TO BE | | PROVIDED FOR PERMANENT MEANS OF ACCESS. | | PLEASE PROVIDE SUBMITTAL DATA FOR THE | | LADDER AS WELL AS A DETAIL FOR THE | | ATTACHMENT OF THE LADDER TO THE | | BUILDING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|