2006-01-06 00:00:00********** UNSAT ***********
  
  
 1)NOTE: PLEASE KNOW, ELECTRICAL AND
 MECHANICAL AND PLUMBING PLANS ARE NOW
 COMING IN SIGNED,SEALED BY AN ARCHITECT.
 THIS IS ASSUMING THE WORK OF ANOTHER
 DESIGNER. PLEASE SEE THE ORIGINAL
 DESIGNER OF RECORD WHICH WAS AN ENGINEER
 IS STILL SHOWN ON PLANS AND ALSO
 CONTAINS A PHOTOCOPY OF THE ORIGINAL
 SIGNATURE AND SEALED BY SAID ENGINEER OF
 RECORD.
 PLEASE SEE FS 481.221 (5)(6) WHICH
 STATES:
 (5) NO REGISTERED INTERIOR DESIGNER
 SHALL AFFIX, OR PERMIT TO BE AFFIXED,
 HER OR HIS SEAL OR SIGNATURE TO ANY
 PLAN, SPECIFICATION, DRAWING, OR OTHER
 DOCUMENT WHICH DEPICTS WORK WHICH SHE OR
 HE IS NOT COMPETENT OR LICENSED TO
 PERFORM.
  
 (6)NO REGISTERED ARCHITECT SHALL AFFIX
 HER OR HIS SIGNATURE OR SEAL TO ANY
 FINAL CONSTRUCTION DOCUMENT OR
 INSTRUMENT OF SERVICE WHICH INCLUDES
 DRAWINGS, PLANS, SPECIFICATIONS, OR
 ARCHITECTURAL DOCUMENTS WHICH WERE NOT
 PREPARED BY HER OR HIM OR UNDER HER OR
 HIS RESPONSIBLE SUPERVISING CONTROL OR
 BY ANOTHER REGISTERED ARCHITECT AND
 REVIEWED, APPROVED, OR MODIFIED AND
 ADOPTED BY HER OR HIM AS HER OR HIS OWN
 WORK ACCORDING TO RULES ADOPTED BY THE
 BOARD.
  
 ** PLEASE KNOW THE ORIGINAL DESIGNER'S
 OF RECORD HAVE BEEN CONTACTED AND ONE
 COPY OF SAID PLANS ARE BEING RETAINED
 FOR FILE FOR REVIEW BY THE STATE BOARD
 OF ARCHITECT'S.
 THIS HAS BEEN CONFIRMED WITH THE
 BUILDING OFFICAL.
 IT WAS MENTIONED TO THE ELECTRICAL
 CONTRACTOR AND OWNER OF RECORD IN A
 MEETING BEFORE PLANS WERE RE-SUBMITTED
 THE PLANS NEEDED TO GO BACK TO THE
 ORIGINAL DESIGNER OF RECORD FOR CHNAGES
 TO PLANS AND BE SIGNED, DATED AND SEALED
 BY THAT DESIGNER.
  
 *********
 PLEASE SEE THE FOLLOWING COMMENTS, SOME
 FROM PREVIOUS REVIEWS AND SOME FROM THIS
 REVIEW.
  
 1)NOTE: PLEASE SEE ROOM/AREA
 DESIGNATIONS WERE ADDED TO PLANS,
 HOWEVER PLEASE SEE MAIN ELECTRICAL RM IS
 SHOWN AS "STOCKRM". PLEASE SEE
 110.26,408.7, 240.24 ETC WHICH DOES NOT
 PERMIT STORAGE WITH THIS ELECTRICAL
 EQUIPMENT.
  
 2)NOTE: PLEASE CORRELATE PANELS WITH
 RISER DIAGRAM, ONE SHOWS 125A AND OTHERS
 SHOW 100A.
 215.5
 PREVIOUS NOTES.
  
 3)NOTE: PLEASE SEE RISER IS NOW SHOWING
 CONDUCTORS BEING INSTALLED TO THE
 "FUTURE" METERS AND MAINS? THESE WOULD
 NO LONGER BE "FUTURE". PLEASE ADJUST AND
 COMPLETE RISER ACCORDINGLY.
  
 4)NOTE: PLEASE SEE KITCHEN/BREAK AREA
 SHALL HAVE GFI PROTECTION FOR ALL 15/20A
 120V RECEPTS.
  
 5)NOTE: PLEASE SEE FS 553.80(2)(B) WHICH
 IS STILL IN EFFECT.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWERS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  