Plan Review Notes
Plan Review Notes For Permit 05070295
Permit Number 05070295
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-10 00:00:00*********** UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE THERE ARE NUMEROUS CIRCUITS
 ON PLANS WHICH DO NOT CORRELATE.
 PLEASE SEE
 A-5 SHOWN AS SIGN CIR AND SHOWN AS
 RECEPTS ON PLANS.
 PLEASE SEE STORE AREA SHOWS CIRCUITS TO
 PANEL "A" FOR LIGHTING , HOWEVER PANEL
 "A" IF FOR A SEPRATE SPACE.
 PLEASE ALSO SEE 700.12E WHICH REQUIRES
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SE SOME CIRCUITS SHOWN ON PLANS,
 NOTHING IS SHOWN ON PANEL SCHEDULE.
 PLEASE SEE REDLINED PLANS FOR OTHER
 ITEMS.
  
 2)NOTE: PLEASE SEE PLANS STILL MISSING
 ROOM/ AREA DESIGNATIONS ON PLANS.
 OFFICE/STORAGE, BATHS, KITCHENS ETC.
  
 3)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15/20A 125V RECEPTS
 IN KTICHEN AREAS OFNON-DWELLING UNIT
 TO BE GFI/GFI PROTECTED. THIS IS
 REQUIRED WHETHER OR NOT RECEPT SERVES
 COUNTERSPACE.
  
 4)NOTE: PLEASE SEE MIN VA FOR WINDOW
 LINEAR FT. 200 VA PER FT. SCALE SEEMS TO
 INDICATES 22' +/-. 220.12
  
 5)NOTE: PLEASE CORRELATE PANELS ON RISER
 WITH PANEL SCHEDULES. 100A/125A,
 100A/125A??
 215.5
  
 6)NOTE: PLEASE INDICATE CONDUCTORS FROM
 GUTTER TO EACH NEW METER AND FROM METER
 TO MAINS.
 215.5,215.3,240.4,310.16, ETC
 PLEASE BE SURE "EQUIPMENT GROUNDING
 CONDUCTORS" ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT. 250.6
  
 7)NOTE: PLEASE SEE RISER INDICATES
 GROUNDING ELECTRODE TO FOOTER STEEL. ??
 THIS SEEMS TO BE AN EXISTING BLDG AND
 FOOTER STEEL WOULD NOT BE REQUIRED TO AN
 EXISTING BLDG, HOWEVER MAY BE DONE.
 IF THIS IS SHOWN, THEN IT WILL BE
 REQUIRED.
 PLEASE SEE THAT 2-GRND RODS WILL BE
 REQUIRED.
 250.50
  
  
 8)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONALS AND PLANS WITH
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
  
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEW(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]