2005-09-10 00:00:00 | *********** UNSAT 2ND REVIEW ********** |
| |
| PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH PANEL SCHEDULES |
| SUBMITTED. |
| PLEASE SEE THERE ARE NUMEROUS CIRCUITS |
| ON PLANS WHICH DO NOT CORRELATE. |
| PLEASE SEE |
| A-5 SHOWN AS SIGN CIR AND SHOWN AS |
| RECEPTS ON PLANS. |
| PLEASE SEE STORE AREA SHOWS CIRCUITS TO |
| PANEL "A" FOR LIGHTING , HOWEVER PANEL |
| "A" IF FOR A SEPRATE SPACE. |
| PLEASE ALSO SEE 700.12E WHICH REQUIRES |
| THE BRANCH CIRCUIT FEEDING THE UNIT |
| EQUIPMENT SHALL BE THE SAME BRANCH |
| CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD |
| OF ANY LOCAL SWITCHES. |
| PLEASE SE SOME CIRCUITS SHOWN ON PLANS, |
| NOTHING IS SHOWN ON PANEL SCHEDULE. |
| PLEASE SEE REDLINED PLANS FOR OTHER |
| ITEMS. |
| |
| 2)NOTE: PLEASE SEE PLANS STILL MISSING |
| ROOM/ AREA DESIGNATIONS ON PLANS. |
| OFFICE/STORAGE, BATHS, KITCHENS ETC. |
| |
| 3)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| WHICH REQUIRES ALL 15/20A 125V RECEPTS |
| IN KTICHEN AREAS OFNON-DWELLING UNIT |
| TO BE GFI/GFI PROTECTED. THIS IS |
| REQUIRED WHETHER OR NOT RECEPT SERVES |
| COUNTERSPACE. |
| |
| 4)NOTE: PLEASE SEE MIN VA FOR WINDOW |
| LINEAR FT. 200 VA PER FT. SCALE SEEMS TO |
| INDICATES 22' +/-. 220.12 |
| |
| 5)NOTE: PLEASE CORRELATE PANELS ON RISER |
| WITH PANEL SCHEDULES. 100A/125A, |
| 100A/125A?? |
| 215.5 |
| |
| 6)NOTE: PLEASE INDICATE CONDUCTORS FROM |
| GUTTER TO EACH NEW METER AND FROM METER |
| TO MAINS. |
| 215.5,215.3,240.4,310.16, ETC |
| PLEASE BE SURE "EQUIPMENT GROUNDING |
| CONDUCTORS" ARE ONLY INSTALLED AFTER THE |
| FIRST MEANS OF DISCONNECT. 250.6 |
| |
| 7)NOTE: PLEASE SEE RISER INDICATES |
| GROUNDING ELECTRODE TO FOOTER STEEL. ?? |
| THIS SEEMS TO BE AN EXISTING BLDG AND |
| FOOTER STEEL WOULD NOT BE REQUIRED TO AN |
| EXISTING BLDG, HOWEVER MAY BE DONE. |
| IF THIS IS SHOWN, THEN IT WILL BE |
| REQUIRED. |
| PLEASE SEE THAT 2-GRND RODS WILL BE |
| REQUIRED. |
| 250.50 |
| |
| |
| 8)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) ATTACHED WITH RESPECT TO |
| DESIGN PROFESSIONALS AND PLANS WITH |
| REPEAT COMMENTS FOR CODE COMPLIANCE. |
| PLEASE SEE THIS IS ONLY A NOTICE GIVEN |
| AT THIS TIME. |
| |
| |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| OTHER REVIEW(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |