2005-10-14 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT:05070295 |
| ADD: 1256 PALM BEACH LAKES BLVD |
| CONT: MASTER CONTRACTORS |
| TEL: (561)712-8898 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS NOW INDICATE A TRUE TENENT |
| SEPERATION WALL. PROVIDE A 1HR RATED |
| WALL ASSEMBLY (UL OR EQUIVALENT)TO THE |
| METAL ROOF DECK.704.1.1. |
| |
| 2)PROVIDE THIS INFORMATION ON PLAN. |
| 704.2.1.4 CORRIDOR PARTITIONS, SMOKESTOP |
| PARTITIONS, HORIZONTAL EXIT PARTITIONS, |
| EXIT ENCLOSURES, AND FIRE RATED WALLS |
| REQUIRED TO HAVE PROTECTED OPENINGS |
| SHALL BE EFFECTIVELY AND PERMANENTLY |
| IDENTIFIED WITH SIGNS OR STENCILING IN A |
| MANNER ACCEPTABLE TO THE AUTHORITY |
| HAVING JURISDICTION.SUCH |
| IDENTIFICATION SHALL BE ABOVE ANY |
| DECORATIVE CEILING AND IN CONCEALED |
| SPACES.SUGGESTED WORDING:FIRE AND |
| SMOKE BARRIER PROTECT ALL OPENINGS. |
| |
| 3)ND ROOF DECK.(UL OR |
| EQUIVALENT) PROVIDE A FLEXIBLE JOINT |
| FIRE AND |
| SMOKE ASSEMBLY AT THE TENANT SEPERATION |
| BETWEEN WALL A |
| 705.7.1 JOINTS INSTALLED IN OR BETWEEN |
| FIRE RESISTANT WALLS, FIRE RESIS- TANT |
| FLOORS OR FLOOR/ CEILING ASSEMBLIES AND |
| FIRE RESISTANT ROOFS OR ROOF/ CEILING |
| ASSEMBLIES SHALL BE PROTECTED BY AN |
| APPROVED FIRE RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE |
| FOR A PERIOD NOT LESS THAN THE REQUIRED |
| FIRE RESISTANCE RATING OF THE WALL, |
| FLOOR OR FLOOR IN OR BETWEEN |
| WHICH IT IS INSTALLED. |
| |
| 4) DISCREPANCY BETWEEN THE A-2 & THE |
| MEP-1 SHEET THE NEW OFFICE DOORS ARE IN |
| DIFFERENT WALLS, PLEASE CORRECT. |
| |
| 5) NEW OFFICE LOOKS LIKE THERE IS A |
| KITCHEN AREA, IF SO COMPLY WITH: |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| |
| 6A) PRODUCT APPROVALS, THE ARCH EXTERIOR |
| DOORS AND PANEL WALL SYSTEMS SUBMITTED |
| WILL REQUIREA HURRICANE PROTECTIVE |
| SYSTEM. PROVIDE PRODUCT APPROVAL REPORT |
| FOR STORM SHUTTERS WITH A FL COVER |
| SHEET. |
| PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| 6B) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| THE DOOR SCHEDULE INDICATES DOOR# 3 TO |
| BE A HOLLOW CORE METAL CLAD DOOR, WHERE |
| AS THE FLOOR PLAN & ELEVATIONS INDICATE |
| GLASS DOORS WITH SIDE LIGHTS. |
| 6C) 2405.2.1 THE FOLLOWING SHALL BE |
| CONSIDERED SPECIFIC HAZARDOUS LOCATIONS |
| FOR THE PURPOSES OF GLAZING: |
| |
| 1. GLAZING IN SWINGING DOORS AND |
| FIXED AND SLIDING PANELS OF SLIDING |
| (PATIO) DOOR ASSEMBLIES. |
| |
| 2. GLAZING IN DOORS AND WALLS OF |
| ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, |
| SAUNAS, STEAM ROOMS, BATHTUBS, |
| SHOWERS AND OTHER SUCH FACILITIES |
| WHERE SUCH GLAZING IS LOCATED 36 |
| INCHES (914 MM) OR LESS, MEASURED |
| HORIZONTALLY, FROM A STANDING OR |
| WALKING SURFACE WITHIN THE ENCLOSURE |
| AND WHERE THE BOTTOM EDGE OF THE |
| EXPOSED GLAZING IS LESS THAN 60 |
| INCHES (1524 MM), MEASURED |
| VERTICALLY, ABOVE SUCH STANDING OR |
| WALKING |
| SURFACES. |
| |
| 3. GLAZING IN AN INDIVIDUAL FIXED OR |
| OPERABLE PANEL ADJACENT TO A DOOR |
| WHERE THE NEAREST VERTICAL EDGE |
| IS WITHIN A 24-INCH (610 MM) RADIUS |
| OF THE DOOR IN A CLOSED POSITION |
| AND WHOSE BOTTOM EDGE IS LESS THAN |
| 60 INCHES (1524 MM) ABOVE THE |
| FLOOR OR WALKING SURFACE. |
| |
| |
| |
| 7)BEFORE THIS PERMIT IS ISSUED,TO |
| PERMITS HAVE TO BE ISSUED, SEE |
| ATTACHMENTS: |
| 7A) INTERIOR DEMO PERMIT |
| 7B) EXTERIOR STUCCO |
| IN BOTH CASES THE WORK HAS BEEN |
| COMPLETED WITHOUT THE BENIFET OF A |
| PERMIT!!!!!!!! |
| |
| 8) PLANS INDICATE EXISTING HANDICAPPED |
| RAMP PROVIDE HEIGHT OF THE EXISSTING |
| RAMP AND CONFIGURATION. MAY REQUIRE |
| UPGRADES, SEE 11-4.8 SLOPE, RISE, |
| LANDINGS AND HANDRAILS. |
| 11-4.8.8 OUTDOOR CONDITIONS. OUTDOOR |
| RAMPS AND THEIR APPROACHES SHALL |
| BE DESIGNED SO THAT WATER WILL NOT |
| ACCUMULATE ON WALKING SURFACES. |
| NOTE: |
| 11-4.1.6(2) DUTY TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| AREAS SHALL BE DEEMED DISPROPORTIONATE |
| TO THE OVERALL ALTERATION WHEN THE COST |
| EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| TION TO THE PRIMARY FUNCTION AREA. |
| (A)(I) AN ACCESSIBLE ENTRANCE |
| (II) AN ACCESSIBLE ROUTE |
| (III) AT LEAST ONE ACCESSIBLE REST- |
| ROOM FOR EACH SEX OR A SINGLE |
| UNISEX RESTROOM |
| (IIII) ACCESSIBLE TELEPHONE |
| (IV) ELEMENTS SUCH AS PARKING, STOR- |
| AGE OR ALARMS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |