2005-10-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:05070295
 ADD: 1256 PALM BEACH LAKES BLVD
 CONT: MASTER CONTRACTORS
 TEL: (561)712-8898
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS NOW INDICATE A TRUE TENENT
 SEPERATION WALL. PROVIDE A 1HR RATED
 WALL ASSEMBLY (UL OR EQUIVALENT)TO THE
 METAL ROOF DECK.704.1.1.
  
 2)PROVIDE THIS INFORMATION ON PLAN.
 704.2.1.4 CORRIDOR PARTITIONS, SMOKESTOP
 PARTITIONS, HORIZONTAL EXIT PARTITIONS,
 EXIT ENCLOSURES, AND FIRE RATED WALLS
 REQUIRED TO HAVE PROTECTED OPENINGS
 SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A
 MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION.SUCH
 IDENTIFICATION SHALL BE ABOVE ANY
 DECORATIVE CEILING AND IN CONCEALED
 SPACES.SUGGESTED WORDING:FIRE AND
 SMOKE BARRIER PROTECT ALL OPENINGS.
  
 3)ND ROOF DECK.(UL OR
 EQUIVALENT) PROVIDE A FLEXIBLE JOINT
 FIRE AND
 SMOKE ASSEMBLY AT THE TENANT SEPERATION
 BETWEEN WALL A
 705.7.1 JOINTS INSTALLED IN OR BETWEEN
 FIRE RESISTANT WALLS, FIRE RESIS- TANT
 FLOORS OR FLOOR/ CEILING ASSEMBLIES AND
 FIRE RESISTANT ROOFS OR ROOF/ CEILING
 ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE REQUIRED
 FIRE RESISTANCE RATING OF THE WALL,
 FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 4) DISCREPANCY BETWEEN THE A-2 & THE
 MEP-1 SHEET THE NEW OFFICE DOORS ARE IN
 DIFFERENT WALLS, PLEASE CORRECT.
  
 5) NEW OFFICE LOOKS LIKE THERE IS A
 KITCHEN AREA, IF SO COMPLY WITH:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 6A) PRODUCT APPROVALS, THE ARCH EXTERIOR
 DOORS AND PANEL WALL SYSTEMS SUBMITTED
 WILL REQUIREA HURRICANE PROTECTIVE
 SYSTEM. PROVIDE PRODUCT APPROVAL REPORT
 FOR STORM SHUTTERS WITH A FL COVER
 SHEET.
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 6B) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE DOOR SCHEDULE INDICATES DOOR# 3 TO
 BE A HOLLOW CORE METAL CLAD DOOR, WHERE
 AS THE FLOOR PLAN & ELEVATIONS INDICATE
 GLASS DOORS WITH SIDE LIGHTS.
 6C) 2405.2.1 THE FOLLOWING SHALL BE
 CONSIDERED SPECIFIC HAZARDOUS LOCATIONS
 FOR THE PURPOSES OF GLAZING:
  
 1. GLAZING IN SWINGING DOORS AND
 FIXED AND SLIDING PANELS OF SLIDING
 (PATIO) DOOR ASSEMBLIES.
  
 2. GLAZING IN DOORS AND WALLS OF
 ENCLOSURES FOR HOT TUBS, WHIRLPOOLS,
 SAUNAS, STEAM ROOMS, BATHTUBS,
 SHOWERS AND OTHER SUCH FACILITIES
 WHERE SUCH GLAZING IS LOCATED 36
 INCHES (914 MM) OR LESS, MEASURED
 HORIZONTALLY, FROM A STANDING OR
 WALKING SURFACE WITHIN THE ENCLOSURE
 AND WHERE THE BOTTOM EDGE OF THE
 EXPOSED GLAZING IS LESS THAN 60
 INCHES (1524 MM), MEASURED
 VERTICALLY, ABOVE SUCH STANDING OR
 WALKING
 SURFACES.
  
 3. GLAZING IN AN INDIVIDUAL FIXED OR
 OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE
 IS WITHIN A 24-INCH (610 MM) RADIUS
 OF THE DOOR IN A CLOSED POSITION
 AND WHOSE BOTTOM EDGE IS LESS THAN
 60 INCHES (1524 MM) ABOVE THE
 FLOOR OR WALKING SURFACE.
  
  
  
 7)BEFORE THIS PERMIT IS ISSUED,TO
 PERMITS HAVE TO BE ISSUED, SEE
 ATTACHMENTS:
 7A) INTERIOR DEMO PERMIT
 7B) EXTERIOR STUCCO
 IN BOTH CASES THE WORK HAS BEEN
 COMPLETED WITHOUT THE BENIFET OF A
 PERMIT!!!!!!!!
  
 8) PLANS INDICATE EXISTING HANDICAPPED
 RAMP PROVIDE HEIGHT OF THE EXISSTING
 RAMP AND CONFIGURATION. MAY REQUIRE
 UPGRADES, SEE 11-4.8 SLOPE, RISE,
 LANDINGS AND HANDRAILS.
 11-4.8.8 OUTDOOR CONDITIONS. OUTDOOR
 RAMPS AND THEIR APPROACHES SHALL
 BE DESIGNED SO THAT WATER WILL NOT
 ACCUMULATE ON WALKING SURFACES.
 NOTE:
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026