Plan Review Notes For Permit 05070295 |
Permit Number |
05070295 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-27 00:00:00 | DENIED: | | 1.PLAN SHEET MEP4 MOUNTING DETAIL FOR | | THE RTU.PER 2001 FBC 1511.7, CURB | | SHALL BE A MINIMUM OF 8" ABOVE THE | | FINISHED ROOF. | | | | 2.OUTSIDE AIR CALCULATION INDICATES | | 3260 CFM REQUIRED, EQUIPMENT SCHEDULE | | INDICATES ONLY 1128 CFM PROVIDED. | | | | 3.CLARIFY ACCESS TOEQUIPMENT LOCATED | | ON THE ROOF.PER 2001 FBC(M) 306.5 | | PERMANENT ACCESS REQUIRED FOR HEIGHTS | | GREATER THAN 16 FT. | | | | 4.ARICHETECT SEAL IS NOT LEGIBLE AS | | REQUIRED BY FAC 61G1-16.004 & FS 481.221 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|