Notes
Date Text
2005-08-11 00:00:00******DENIED******
  
 1) PLEASE SHOW ADDRESS ON BUIDING
 WHETHER NEW OR EXISTING THAT SHALL BE AT
 LEAST 6" IN HEIGHT AND CONTRASTING TO
 THE BACKGROUND.
  
 2) PLEASE SHOW LOCATION OF 2A-10B,C
 RATED FIRE EXTINGUISHERS THAT MUST BE
 MOUNTED DISTANCES THAT MEET THE 75'
 TRAVEL DISTANCE REQUIREMENT.
  
 3) PLEASE PROVIDE OCCUPANCY
 CLASSIFICATION.
  
 4) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  