Plan Review Notes
Plan Review Notes For Permit 05070295
Permit Number 05070295
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-25 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 215.5
 PLEASE BES URE TO SEE 700.12E FOR
 CIRCUITING OF EM.EXT LTS.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS SUBMITTED. 400A? 150A?
 215.5
  
 3)NOTE: PLEASE SEE 240.4,310.16 FOR MIN
 SIZE OF FEEDERS TO PANEL "L" WHICH IS
 SHOWN BEING FED FROM 400A OCP.
 PLEASE SEE OTHER TWO FEEDERS TO SUB
 PANELS INDICATE #3 MCM? PLEASE SEE AWG
 FOR SIZES AND DISCRIPTION OF CONDUCTORS.
 THERE IS NO #3 MCM.
  
 4)NOTE: PLEASE SEE 250.122 FOR SIZING OF
 EQUIPMENT GROUNDING CONDUCTORS.
 PLEASE SEE MAIN TO PANEL "L".
  
 5)NOTE: PLEASE SEE PLANS SHALL BE
 SIGNED, DATED AND SEALED BY THE ENGINEER
 RESPONSIBLE FOR DESIGN.
 FS 471.025
  
 6)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED IN TITLE BLOCK FOR ARCHITECT.
 PLEASE SEE SEAL SHALL BE CLEAR AND
 VISABLE AS REQUIRED UNDER FS 481.221.
 PLEASE SEE FAC 61G1-16.004 FOR MISSING
 INFORMATION.
  
 7)NOTE: PLEASE CLARIFY IF SERVICE SHOWN
 IS NEW OR EXSITNG??
 PLEASE SEE ONE MAIN IS SHOWN FOR
 "FUTURE", HOWEVER PANEL IS BEING SHOWN
 AS NEW AT THIS TIME. HOW IS THIS PANEL
 FED IF MAIN/ METER IS "FUTURE"
  
 8)NOTE: PLEASE SEE 250.66 FIR MIN
 GROUNDING ELECTRODE CONDUCTOR.
 2/0MIN.
  
 9)NOTE: PLEASE SHOW ALLELECTRICAL
 EQUIPMENT ON PLANS. ALL MAINS, PANELS
 NEED TO BE SHOWN AT LOCATIONS ON PLANS.
 215.5
  
 10)NOTE: PLEASE SEE AREAS ON PLANS WHERE
 NO ELECTRICAL IS SHOWN? LTS?
  
 11)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
  
 12)NOTE: PLEASE SEE 210.62,220.12 FOR
 MIN "SHOW ROOM" WINDOW RECEPTS REQUIRED.
  
 13)NOTE: PLEASE SEE SOME ITEMS LISTED ON
 PANEL SCHEDULE, HOWEVER THESE ITEMS
 COULD NOT BE LCOATED ON PLANS?
 PARKING LTO LTS, IRRIGATION PUMP ETC.??
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  