Text |
2005-07-25 00:00:00 | ************* UNSAT *************** |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH PANEL SCHEDULES |
| SUBMITTED. |
| 215.5 |
| PLEASE BES URE TO SEE 700.12E FOR |
| CIRCUITING OF EM.EXT LTS. |
| |
| 2)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| WITH PANELS SUBMITTED. 400A? 150A? |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE 240.4,310.16 FOR MIN |
| SIZE OF FEEDERS TO PANEL "L" WHICH IS |
| SHOWN BEING FED FROM 400A OCP. |
| PLEASE SEE OTHER TWO FEEDERS TO SUB |
| PANELS INDICATE #3 MCM? PLEASE SEE AWG |
| FOR SIZES AND DISCRIPTION OF CONDUCTORS. |
| THERE IS NO #3 MCM. |
| |
| 4)NOTE: PLEASE SEE 250.122 FOR SIZING OF |
| EQUIPMENT GROUNDING CONDUCTORS. |
| PLEASE SEE MAIN TO PANEL "L". |
| |
| 5)NOTE: PLEASE SEE PLANS SHALL BE |
| SIGNED, DATED AND SEALED BY THE ENGINEER |
| RESPONSIBLE FOR DESIGN. |
| FS 471.025 |
| |
| 6)NOTE: PLEASE SEE MISSING INFORMATION |
| REQUIRED IN TITLE BLOCK FOR ARCHITECT. |
| PLEASE SEE SEAL SHALL BE CLEAR AND |
| VISABLE AS REQUIRED UNDER FS 481.221. |
| PLEASE SEE FAC 61G1-16.004 FOR MISSING |
| INFORMATION. |
| |
| 7)NOTE: PLEASE CLARIFY IF SERVICE SHOWN |
| IS NEW OR EXSITNG?? |
| PLEASE SEE ONE MAIN IS SHOWN FOR |
| "FUTURE", HOWEVER PANEL IS BEING SHOWN |
| AS NEW AT THIS TIME. HOW IS THIS PANEL |
| FED IF MAIN/ METER IS "FUTURE" |
| |
| 8)NOTE: PLEASE SEE 250.66 FIR MIN |
| GROUNDING ELECTRODE CONDUCTOR. |
| 2/0MIN. |
| |
| 9)NOTE: PLEASE SHOW ALLELECTRICAL |
| EQUIPMENT ON PLANS. ALL MAINS, PANELS |
| NEED TO BE SHOWN AT LOCATIONS ON PLANS. |
| 215.5 |
| |
| 10)NOTE: PLEASE SEE AREAS ON PLANS WHERE |
| NO ELECTRICAL IS SHOWN? LTS? |
| |
| 11)NOTE: PLEASE SHOW ALL ROOM/AREA |
| DESIGNATIONS ON PLANS. |
| |
| 12)NOTE: PLEASE SEE 210.62,220.12 FOR |
| MIN "SHOW ROOM" WINDOW RECEPTS REQUIRED. |
| |
| 13)NOTE: PLEASE SEE SOME ITEMS LISTED ON |
| PANEL SCHEDULE, HOWEVER THESE ITEMS |
| COULD NOT BE LCOATED ON PLANS? |
| PARKING LTO LTS, IRRIGATION PUMP ETC.?? |
| |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED |
| SHEETS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |