2005-07-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1606.1.4SHUTTERS.
 INSTALLATION/DESIGN INFORMATION
 REQUIRED.SUBMIT AN INSTALLATION
 SCHEDULE INCLUDING THE FOLLOWING
 DETAILS:
 (A) BUILDING CONSTRUCTION TYPE (EG CBS)
 (B) BUILDING (OR INSTALLATION) HEIGHT
 (C) DESIGN PRESSURE FOR EACH OPENING
 (D) OPENING SIZES
 (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?)
 (F) ANCHOR TYPE, SIZE AND SPACING
 A FORM IS AVAILABLE FROM THIS OFFICE
 GIVING THE RECOMMENDED INSTALLATION
 SCHEDULE FORMAT.SUBMIT THE ABOVE
 INFORMATION WHICH IS REQUIRED FOR
 REVIEW.A COPY OF THE RECOMMENDED
 INSTALLATION SCHEDULE FORM IS ATTACHED.
  
 2) THE SUBMITTED STATEWIDE PRODUCT
 APPROVAL FL1850 REFERS TO DRAWING
 03-0135.THE VERSION OF THAT DRAWING ON
 THE STATEWIDE PRODUCT APPRVAL WEBSITE
 INCLUDES THE SIGNATURE AND SEAL OF
 WALTER A. TILLIT JR. P.E.THE TWO
 COPIES SUBMITTED FOR REVIEW DO NOT
 INCLUDE THE SIGNATURE AND SEAL AND SO
 CANNOT BE VERIFIED AS HAVING BEEN
 PREPARED/REVIEWED BY THE ENGINEER.
 DOWNLOAD AND SUBMIT TWO COPIES OF
 DRAWING 03-0135 SO THAT THEY ARE AN
 EXACT MATCH FOR THAT APPROVED BY THE
 STATE.
  
 3) SOME THE OPTIONS COVERED BY THE
 SUBMITTED PRODUCT APPROVALS MAY NOT BE
 CODE COMPLIANT IF USED FOR THIS PROJECT.
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/SPANS/FASTENERS
 AND ANCHORING CONDITIONS ARE TO BE USED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]