2005-08-01 00:00:00DENIED;
 1.POOL COMPLIES WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS (ADD TO NOTES)
 2.SEC. 424.2.6/1 ENGINEERING DESIGN,
 CONSTRUCTION AND WORKMANSHIP PER.
 ANSI/NSPI-5 (ADD TO NOTES)
 3.SEC.424.2.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF. INFORMATION FOR
 VAC.LOCK. (GIVE DETAIL , SUBMITTLE OR
 ADD TO NOTES)
 4.SEC.424.2.8/1 -4 VALVES SHALL BE
 APPROVED BY FBC-2001.THEY WILL BE
 READILY ACCESSIBLE FOR MAINT. AND
 REMOVAL. FULL WAY VALVES SHALL BE
 INSTALLED. WHERE CHECK VALVES ARE
 INSTALLED THEY SHALL OF THE SWING OR
 VERTICAL CHECK PATTERNS.
 5.SEC.424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 6.SEC.424.2.12.1PRESSURE TESTS. PER.
 MANUFACTURE RECOMMENDATIONS, NO AIR TEST
 SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7.SEC.424.2.13.2 JOINTS AND CONNECTIONS.
 FBC PLUMBING SEC. 605.21, PURPLE PRIMER
 REQUIRED ON PVC PIPE. (ADD TO NOTES)
 8.SEC.424.2.15 GAS PIPING SHALL COMPLY
 WITH FBC 2001 FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.