Plan Review Notes For Permit 05070247 |
Permit Number |
05070247 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-18 00:00:00 | DENIED: | | 1.PROVIDE MANUFACTURER'S SUBMITTAL | | DATA FOR THE GENERATOR. | | | | 2.PROVIDE ELEVATION TO BOTTOM OF THE | | MUFFLER EXHAUST PIPE RUNNING THROUGH THE | | PARKING GARAGE. | | | | 3.PROVIDE DISTANCE PROPERTY LINES. | | SHOW COMPLIANCE WITH 2001 FBC(M)401.5 | | | | 4.EXHAUST OPENINGS SHALL NOT BE | | DIRECTED ONTO WALKWAYS PER 2001 | | FBC(M)401.5.2.PLEASE NOTE, EXHAUST | | SHALL TERMINATE IN SUCH A MANNER THAT IT | | WILL NOT RECIRCULATE INTO THE GARAGE, | | FRESH AIR INTAKES, WINDOWS, DOORS, OR | | VENTILATING SYSTEMS. | | | | 5.PLAN INDICATES FUEL PIPING THROUGH | | THE ELECTRICAL VAULT, PLEASE CLARIFY. | | | | 6.PLEASE CLARIFY AREA IN WHICH EF-3 | | TERMINATES.IS THIS A PARKING AREA? | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | |
|