Plan Review Notes
Plan Review Notes For Permit 05070246
Permit Number 05070246
Review Stop P
Sequence Number 2
Notes
Date Text
2005-09-10 00:00:00DENIED;
 1.PLAN CHANGES NEED TO BE DONE BY THE
 ENGINEER OF RECORD. SEE THE CITY OF WEST
 PALM BEACH AMENDMENTS TO THE FBC CHAPTER
 1 SEC 104.2. DELETE ALL UNUSED DIAGRAMS
 AND DRAW NEW RISER DIAGRAM SHOWING ALL
 EQUIPMENT TO BE INSTALLED AND IN WHAT
 ORDER.
 2.ON FRONT PAGE SHOW ALL PIPING AROUND
 POOL TO EQUIPMENT. SIZE ALL PIPE SHOW
 MAIN DRAIN VENTS TO TERMINATION POINT.
 3. PROVIDE A MANUFACTOR'S CUT SHEET ON
 POOL HEATER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695