Plan Review Notes
Plan Review Notes For Permit 05070242
Permit Number 05070242
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-10 00:00:00*********** UNSAT ***************
  
  
 1)NOTE: PLEASE CORRELAT ALL ELECTRICAL
 AND PLUMB PLANS SUBMITTED.
 PLEASE SEE PLUMB PLANS SHOWS NEW 5HP
 PUMPS FOR FOUNTAINS AND ELECTRICAL SHOWS
 2- 2HP PUMPS??
 PLEASE SEE THE FOLLOWING COMMENTS.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 EXISTING 200A PANEL DOES NOT INCLUDE ANY
 OCP , CONDUIT OR FEEDER SIZES TO NEW
 PANEL.?
 240.4,310.16, ETC.
 PLEASE ALSO SEE THIS PANEL SHOWS 2-P20A
 BRKR FEEDING 5HP PUMP.
 PLEASE SEE NEC MIN OCP, AWG 430.148.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 PANEL AS EXISTING , YET RISER SHOWS THIS
 PANEL AS BEING NEW? PLEASE CORRELATE.
  
 4)NOTE: PLEASE SIZE OVERCURRENT
 PROTECTION, CONDUCTOR SIZES ETC FOR
 ??WHICH SIZE PUMPS WILL BE INSTALLED.
  
 5)NOTE: PLEASE SEE CONTINUOUS LOADS ARE
 SHOWN AS 125% FOR BOTH PUMPS OR ANY
 LOADS, 3 OR MORE HRS. PLEASE SEE THE
 ADDITIONAL 125% IS THEN FIGURED ABOVE
 FOR LARGEST MOTOR.
 PANEL SCHEDULE ONLY SHOWS CONTINUOUS
 LOAD FOR ONE MOTOR.
 215.3,230.42 ETC.
  
 6)NOTE: PLEASE SEE ONLY ONE TIME CLOCK
 IS SHOWN FOR BOTH MOTORS, THIS MAY
 CHANGE ONCE PUMP SIZE CORRELATES AND IS
 DETERMINED.
 IF 5HP, ONE TCV WILL NOT BE LARGE ENOUGH
 FOR BOTH, UNLESS THIS FEEDE STARTER
 CONTACTORS.
 THIS IS ONLY A NOTE , AS COORDINATION
 ISSUES STILL NED TO BE ADDRESSED.
  
 7)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) IS NOW ATTACHED WITH
 RESPECT TO DESIGN PROFESSIONAL AND PLANS
 WITH REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 8)NOTE: PLEASE SEE THAT 2-GRND RODS WILL
 BE REQUIRED. 250.50,250.56
  
 9)NOTE: PLEASE SEE NEW GFI IS INDICATED
 ON PANEL SCHEDULE, HOWEVER THIS IS NOT
 SHOWN ON PLANS.?
  
 LTR FOR ARCHITECT'S LEGAL SIGNATURE
 RECEIVED AND PLACED IN SIG. FILE.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETED SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  