2005-09-10 00:00:00 | *********** UNSAT *************** |
| |
| |
| 1)NOTE: PLEASE CORRELAT ALL ELECTRICAL |
| AND PLUMB PLANS SUBMITTED. |
| PLEASE SEE PLUMB PLANS SHOWS NEW 5HP |
| PUMPS FOR FOUNTAINS AND ELECTRICAL SHOWS |
| 2- 2HP PUMPS?? |
| PLEASE SEE THE FOLLOWING COMMENTS. |
| |
| 2)NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| EXISTING 200A PANEL DOES NOT INCLUDE ANY |
| OCP , CONDUIT OR FEEDER SIZES TO NEW |
| PANEL.? |
| 240.4,310.16, ETC. |
| PLEASE ALSO SEE THIS PANEL SHOWS 2-P20A |
| BRKR FEEDING 5HP PUMP. |
| PLEASE SEE NEC MIN OCP, AWG 430.148. |
| |
| 3)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS |
| PANEL AS EXISTING , YET RISER SHOWS THIS |
| PANEL AS BEING NEW? PLEASE CORRELATE. |
| |
| 4)NOTE: PLEASE SIZE OVERCURRENT |
| PROTECTION, CONDUCTOR SIZES ETC FOR |
| ??WHICH SIZE PUMPS WILL BE INSTALLED. |
| |
| 5)NOTE: PLEASE SEE CONTINUOUS LOADS ARE |
| SHOWN AS 125% FOR BOTH PUMPS OR ANY |
| LOADS, 3 OR MORE HRS. PLEASE SEE THE |
| ADDITIONAL 125% IS THEN FIGURED ABOVE |
| FOR LARGEST MOTOR. |
| PANEL SCHEDULE ONLY SHOWS CONTINUOUS |
| LOAD FOR ONE MOTOR. |
| 215.3,230.42 ETC. |
| |
| 6)NOTE: PLEASE SEE ONLY ONE TIME CLOCK |
| IS SHOWN FOR BOTH MOTORS, THIS MAY |
| CHANGE ONCE PUMP SIZE CORRELATES AND IS |
| DETERMINED. |
| IF 5HP, ONE TCV WILL NOT BE LARGE ENOUGH |
| FOR BOTH, UNLESS THIS FEEDE STARTER |
| CONTACTORS. |
| THIS IS ONLY A NOTE , AS COORDINATION |
| ISSUES STILL NED TO BE ADDRESSED. |
| |
| 7)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) IS NOW ATTACHED WITH |
| RESPECT TO DESIGN PROFESSIONAL AND PLANS |
| WITH REPEAT COMMENTS. |
| THIS IS ONLY A NOTICE GIVEN AT THIS |
| TIME. |
| |
| 8)NOTE: PLEASE SEE THAT 2-GRND RODS WILL |
| BE REQUIRED. 250.50,250.56 |
| |
| 9)NOTE: PLEASE SEE NEW GFI IS INDICATED |
| ON PANEL SCHEDULE, HOWEVER THIS IS NOT |
| SHOWN ON PLANS.? |
| |
| LTR FOR ARCHITECT'S LEGAL SIGNATURE |
| RECEIVED AND PLACED IN SIG. FILE. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM |
| SETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO COMPLETED SETS FOR REVIEW AND |
| STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |