1 |
|
Notes |
Date |
Text |
2005-08-03 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. INDICATE THE SOURCE OF WATER. IF CITY | | WATER CONNECTION, AND RPZ BACKFLOW | | REQUIRED AND SHOW LOCATION OF | | CONNECTION. SECTIONS 104.2.1 & 608.13.2. | | 2. INDICATE IF A DRAIN LINE FOR THE | | FOUNTAIN WILL BE INSTALLED. SHOW | | LOCATION OF DRAIN AND INDICATE IF PIPING | | TO SEWER AND POINT OF CONNECTION. | | SECTION 104.2.1. & 701.2. | | 3. THE PERSONAL SIGNATURE IS REQUIRED | | PER FAC 61G1-16.003/61G1-16.004(5) AND | | FS 481.2055. IT APPEARS THAT AN INITIAL | | IS BEING USED TO SIGN THE PLANS. PLEASE | | SUBMIT A SIGNED, SEALED, DATED, AND | | NOTORIZED LETTER INDICATING THE LEGAL | | SIGNATURE OF THE DESIGN PROFESSIONAL TO | | REFERENCEFOR OUR FILES. - AS ALWAYS | | ALL SIGNED SEALED INFORMATION IS | | REQUIRED TO HAVE THE TITLE BLOCK | | INFORMATION ON EACH SHEET. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|