Plan Review Notes
Plan Review Notes For Permit 05070242
Permit Number 05070242
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THE SOURCE OF WATER. IF CITY
 WATER CONNECTION, AND RPZ BACKFLOW
 REQUIRED AND SHOW LOCATION OF
 CONNECTION. SECTIONS 104.2.1 & 608.13.2.
 2. INDICATE IF A DRAIN LINE FOR THE
 FOUNTAIN WILL BE INSTALLED. SHOW
 LOCATION OF DRAIN AND INDICATE IF PIPING
 TO SEWER AND POINT OF CONNECTION.
 SECTION 104.2.1. & 701.2.
 3. THE PERSONAL SIGNATURE IS REQUIRED
 PER FAC 61G1-16.003/61G1-16.004(5) AND
 FS 481.2055. IT APPEARS THAT AN INITIAL
 IS BEING USED TO SIGN THE PLANS. PLEASE
 SUBMIT A SIGNED, SEALED, DATED, AND
 NOTORIZED LETTER INDICATING THE LEGAL
 SIGNATURE OF THE DESIGN PROFESSIONAL TO
 REFERENCEFOR OUR FILES. - AS ALWAYS
 ALL SIGNED SEALED INFORMATION IS
 REQUIRED TO HAVE THE TITLE BLOCK
 INFORMATION ON EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]