2005-08-04 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE COMPLETE ELECTRICAL PLANS
 SUBMITTED.
 PLEASE SEE MISSING CONDUCTORS, CONDUITS,
 EQUIPMENT INFORMAITON ON RISER.
 215.5,240.4,310.16, ETC.
 PLEASE SEE NO PANEL SCHEDULE SUBMITTED.
 PLEASE SEE WIRING DIAGRAM FOR FOUNTAIN
 EQUIPMENT NOT COMPLETE WITH WIRING ETC.
 PLEASE SEE A "WATER PUMP" PANEL OF SOME
 SORT IS SHOWN ON RISER, HOWEVER NO
 INFORMAITNO IS PROVIDED FOR THIS?
 PLEASE SEE NOTE ON LOAD CALCS MENTIONS
 FED FROM 200A PANEL, HOWEVER PANEL IS
 SHOWN SHOWN AS 50A?
 215.5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM PER 250.50
 FOOTER STEEL, COLD WATER?
  
 4)NOTE: PLEASE ALSO SEE PLUMB COMMENTS
 WITH REFERENCE TO "LEGAL SIGNATURE" FOR
 ARCH OF RECORD. IF INDEED THIS IN NOT
 INITIALS, PLEASE PROVIDE THE SIGNED,
 DATED SEALED AND NOTORIZED LTR. PLEASE
 SURE LTR CONTAIN ALL INFORMATION FOR A
 NOTORIZED LTR PER FS 117.
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS,
 THIS WAS BROUGHT IN AS A "SIGN PERMIT"
 TYPE. THIS MAY CHANGE.
  
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHALL
 BE SUUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
2005-08-03 00:00:00IN ELECTRICAL FOR REVIEW.
 UNSAT, NOTES TO FOLLOW.