Plan Review Notes For Permit 05070240 |
Permit Number |
05070240 |
|
Review Stop |
E |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2006-02-16 00:00:00 | ***** UNSAT ****** | | | | 1)NOTE: PLEASE CORRELATE PLANS WIHT | | RISER DIAGRAM AND PANEL SCHEDULES. | | PLEASE SEE PANEL "C" SHOWN AS 80AS' ON | | PLANS AND 100A ON SCHEDULE AND RISER. | | 215.5 | | | | 2)NOTE: PLEASE CORRELATE LOAD INDICATED | | ON PANEL "B" WITH LOAD SHOWN ON PANEL | | "A" FOR "B". | | ONE SHOWS 1.9 KW , THE OTHER 4 KW. | | 215.5 | | | | 3)NOTE: PLEASE SEE METER IS SHOWN AS | | 300A'S ON PLANS, AND 320 ON RISER. | | THIS IS A 320A MC WITH A 300A CONTINUOUS | | RATING? | | 215.5 | | | | 4)NOTE: PLEASE SEE REAR PORCH DOES NOT | | INDICATE ANY TYOE OF EGRESS LIGHTING | | FIXTURE AS REQUIRED. PLEASE SEE PLANS | | INDICATE A "J-BOX" AND WIRING FOR FTURE | | FAN/LT , HOWEVER A LT FIXTURE OF SOME | | SORT WILL BE REQUIRED. | | 210.70, LS-101 7.8. | | | | | | 5)NOTE: PLEASE SEE WRONG NEC CODES ARE | | STILL BEING SHOWN ON NOTES FROM THE 1996 | | NEC. | | PLEASE SEE CURRENT NEC 2002, SHOULD BE | | 250.66, AND 250.140 FOR THE TWO | | REFERENCED. | | THIS HAS BEEN REDLINED ON MANY SETS OF | | PLANS, HOWEVER THIS IS NOT BEING | | REVISED. | | 215.5 | | | | | | ** PLEASE REVISE AND SUBMIT THE ABOVE | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|