Plan Review Notes
Plan Review Notes For Permit 05070240
Permit Number 05070240
Review Stop E
Sequence Number 7
Notes
Date Text
2006-02-16 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE CORRELATE PLANS WIHT
 RISER DIAGRAM AND PANEL SCHEDULES.
 PLEASE SEE PANEL "C" SHOWN AS 80AS' ON
 PLANS AND 100A ON SCHEDULE AND RISER.
 215.5
  
 2)NOTE: PLEASE CORRELATE LOAD INDICATED
 ON PANEL "B" WITH LOAD SHOWN ON PANEL
 "A" FOR "B".
 ONE SHOWS 1.9 KW , THE OTHER 4 KW.
 215.5
  
 3)NOTE: PLEASE SEE METER IS SHOWN AS
 300A'S ON PLANS, AND 320 ON RISER.
 THIS IS A 320A MC WITH A 300A CONTINUOUS
 RATING?
 215.5
  
 4)NOTE: PLEASE SEE REAR PORCH DOES NOT
 INDICATE ANY TYOE OF EGRESS LIGHTING
 FIXTURE AS REQUIRED. PLEASE SEE PLANS
 INDICATE A "J-BOX" AND WIRING FOR FTURE
 FAN/LT , HOWEVER A LT FIXTURE OF SOME
 SORT WILL BE REQUIRED.
 210.70, LS-101 7.8.
  
  
 5)NOTE: PLEASE SEE WRONG NEC CODES ARE
 STILL BEING SHOWN ON NOTES FROM THE 1996
 NEC.
 PLEASE SEE CURRENT NEC 2002, SHOULD BE
 250.66, AND 250.140 FOR THE TWO
 REFERENCED.
 THIS HAS BEEN REDLINED ON MANY SETS OF
 PLANS, HOWEVER THIS IS NOT BEING
 REVISED.
 215.5
  
  
 ** PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]