2005-09-23 00:00:00 | ***********UNSAT 3RD REVIEW ******** |
| |
| |
| PLEASE SEE THESE ARE THE EXACT COMMENTS |
| TAKEN FROM REVIEW DONW ON 8/18/05. |
| PLEASE SEE E-SHEETS AND A-SHEETS IN BOTH |
| SETS HAVE NOT BEEN CORRECTED. |
| PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM REVIEW ON 8/18. |
| |
| 1)NOTE: PLEASE SEE SMOKE DETECTOR |
| OUTSIDE MASTER BEDROOM NOT SHOWN? |
| THIS WOULD HAVE BEEN REDLINED, HOWEVER |
| PLEASE SEE NEXT COMMENT. |
| |
| 2)NOTE: PLEASE SEE NEW ELECTRICAL SHEETS |
| IN BOTH SETS WERE NOT DATED OR SEALED BY |
| ARCHITECT OF RECORD AS REQUIRED UNDER FS |
| 481.221. |
| PLEASE ALSO SEE NEW REVISED BLDG SHEETS |
| A-3.1 WHICH IS NOT DATED OR SEALED. |
| PLEASE SEE BLDG REVIEW COMMENTS FOR |
| THIS. |
| |
| 3)NOTE: PLEASE BLDG REVIEW COMMENTS FOR |
| REQUIRED SURVEY TO CONTAIN THE ORIGINAL |
| SIGNATURE OF THE SURVEYOR. PLEASE SEE FS |
| 472.025, FAC 61G17-7.002 |
| PLEASE SEE PLANS ARE COMING BACK FOR |
| ABOVE COMMENTS, PLEASE CORRECT AT THIS |
| TIME. THIS WAS NOT NOTED ON ANY OF THE |
| PREVIOUS REVIEWS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW, IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESIATE IN CONTACTING THIS |
| OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |