Plan Review Notes
Plan Review Notes For Permit 05070240
Permit Number 05070240
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-15 00:00:00BUILDING REVIEW CHECKLIST:
 1- SHEET A-3.1 WAS REVISED BUT ARCHITECT
 FORGOT TO SEAL AND DATE DRAWING AS REQ'D
 BY CHAPTER 481 FL. STATUTES. UNABLE TO
 PASS BUILDING STOP IF ALL DRAWINGS ARE
 NOT SIGNED AND SEALED.
  
 REMAINDER:
 A) CONTRACTOR AGREED TO APPLY FOR
 SHUTTERS UNDER A SEPARATE PERMIT.
 B) CONTRACTOR WILL SUBMIT SHOP DRAWINGS
 FOR STAIRCASE (REVIEWED BY ARCHITECT)
 AFTER FIELD MEASUREMENTS ARE TAKEN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.