Plan Review Notes
Plan Review Notes For Permit 05070240
Permit Number 05070240
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-20 00:00:00***********UNSAT ************
  
 1)NOTE: PELASE CORRELATE RISER DIAGRAM
 WITH PANEL "A". PLEASE SEE PANEL "A" IS
 SHOWN AS 200A MLO AND RISER SHOWS THIS
 AS 225A MCB.
 215.5
  
 2)NOTE: PLEASE SEE SD IN MASTER BEDRM
 NEEDS TO BE MOVED INTOBEDROOM AREA.
 NFPA-72 8-1.4.1.6.2
  
  
 3)NOTE: PLEASE SEE PLANS INDICATE TWO
 GARAGE DOOR OPENERS, HOWEVER ONLY ONE
 CIRCUIT IS SHOWN ON PANEL SCHEDULE FOR
 THESE.
 PLEASE SEE ANY MOTOR LOADS 430.53 WHICH
 MAY REQUIRE A DEDICATED CIRCUIT FOR
 EACH. PLEASE VERIFY HP RATING OF GDO'S.
  
 4)NOTE: PLEASE SEE SMOKE DETECTORS ARE
 SHOWN CIRCUITED TO A-20, HOWEVER THIS
 SPACE IS SHOWN AS SPARE IN PANEL?
 PLEASE ALSO SEE 210.12 OF THE 2002 NEC.
  
 5)NOTE: PLEASE SEE WHIRLPOOL TUB ON
 PANEL SCHEDULE SHOWS GFI PROTECTION AS
 OPTIONAL. PLEASE SEE 680.71, GFI IS
 REQUUIRED.
  
 6)NOTE: PLEASE HAVE ARCHITECT PROVIDE A
 SIGNED, DATED AND SEALED NOTORIZED LTR
 TO VERIFY SIGNATURE ON PLANS IS INDEED
 HIS LEGAL SIGNATURE.
 LTR SHOULD BE PROPERLY NOTORIZED UNDER
 FS 117
 THIS SHALL BE PLACED IN SIGNATURE FILE
 FOR REFERENCE ONLY.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONCE COPY OF OLD SHEETS SHOUDL BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW , IF THERE ARE ANY QUESTIONS,
 PLEASEDO NOT HESITATE TO CALL.
  