2005-07-20 00:00:00 | ***********UNSAT ************ |
| |
| 1)NOTE: PELASE CORRELATE RISER DIAGRAM |
| WITH PANEL "A". PLEASE SEE PANEL "A" IS |
| SHOWN AS 200A MLO AND RISER SHOWS THIS |
| AS 225A MCB. |
| 215.5 |
| |
| 2)NOTE: PLEASE SEE SD IN MASTER BEDRM |
| NEEDS TO BE MOVED INTOBEDROOM AREA. |
| NFPA-72 8-1.4.1.6.2 |
| |
| |
| 3)NOTE: PLEASE SEE PLANS INDICATE TWO |
| GARAGE DOOR OPENERS, HOWEVER ONLY ONE |
| CIRCUIT IS SHOWN ON PANEL SCHEDULE FOR |
| THESE. |
| PLEASE SEE ANY MOTOR LOADS 430.53 WHICH |
| MAY REQUIRE A DEDICATED CIRCUIT FOR |
| EACH. PLEASE VERIFY HP RATING OF GDO'S. |
| |
| 4)NOTE: PLEASE SEE SMOKE DETECTORS ARE |
| SHOWN CIRCUITED TO A-20, HOWEVER THIS |
| SPACE IS SHOWN AS SPARE IN PANEL? |
| PLEASE ALSO SEE 210.12 OF THE 2002 NEC. |
| |
| 5)NOTE: PLEASE SEE WHIRLPOOL TUB ON |
| PANEL SCHEDULE SHOWS GFI PROTECTION AS |
| OPTIONAL. PLEASE SEE 680.71, GFI IS |
| REQUUIRED. |
| |
| 6)NOTE: PLEASE HAVE ARCHITECT PROVIDE A |
| SIGNED, DATED AND SEALED NOTORIZED LTR |
| TO VERIFY SIGNATURE ON PLANS IS INDEED |
| HIS LEGAL SIGNATURE. |
| LTR SHOULD BE PROPERLY NOTORIZED UNDER |
| FS 117 |
| THIS SHALL BE PLACED IN SIGNATURE FILE |
| FOR REFERENCE ONLY. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONCE COPY OF OLD SHEETS SHOUDL BE |
| SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW , IF THERE ARE ANY QUESTIONS, |
| PLEASEDO NOT HESITATE TO CALL. |
| |