2005-09-21 00:00:00DENIED; 2ND TIME
 1) FBC-2001 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)
 2) FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING.THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND
 REMOVAL.SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER
 FUNCTION OF THE FILTRATION AND PIPING
 SYSTEMS.SEC 424.2.8.3 WHERE CHECK
 VALVES ARE INSTALLED THEY SHALL BE OF
 THE SWING OR VERTICAL CHECK PATTERNS.
 SEC 424.2.8.4 COMBINATION VALVES SHALL
 REQUIRE APPROVAL OF THE ADMINISTRATIVE
 AUTHORITY PRIOR TO THEIR INSTALLATION.
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4)424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 5)FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLUMBING SEC. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPING.
 (ADD TO NOTES)
 6)424.2.15 GAS PIPING SHALL COMPLY WITH
 FBC FUEL GAS. SEPARATE PLANS AND PERMIT
 REQUIRED. (ADD TO NOTES)
 PLANS WERE NEVER SENT BACK TO ENGINEER
 FOR REQUESTED CHANGES. ENGINEER'S SEAL
 DATE IS 6/12/05 FIRST REVIEW WAS DONE
 7/26/05. COPY OF FIRST REVIEW INCLOSED.