Plan Review Notes
Plan Review Notes For Permit 05070229
Permit Number 05070229
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-26 00:00:00DENIED;
 1.SEC.424.2.7.1 EQUIPMENT SLAB TO BE
 4"THICK. SHOW ON PLAN
 2.424.2.8.1 VALVESSHALL BE READLY
 ACCESSIBLE FOR MAINT. AND REMOVAL. FULL
 WAY VALVES SHALL BE INSTALLED. WHERE
 CHECK VALVES ARE USED THEY SHALL BEOF
 THE SWING OR VERTICAL CHECK PATTERNS. (
 ADD TO NOTES)
 3.WATER SUPPLY LOCAL ORD. #2853-95,
 BACKFLOW REQUIRED ON WATER SERVICES.
 (ADD TO NOTES)
 4.PRESSURE TESTS. PER. MANUFACTURE
 RECOMMENDATIONS, NO AIR TEST SHALL BE
 APPROVED FOR PVC PIPE AND FITTINGS. (ADD
 TO NOTES)
 5.FBC PLUMBING SEC.605.21 PURPLE PRIMER
 REQUIRED ON PVC PIPE AND FITTINGS. (ADD
 TO NOTES)
 6.424.2.14.4 ALL WATER HEATER EQUIPMENT
 SHALL BE INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO HEATER. (ADD TO
 NOTES)
 7.GAS PIPING SHALL COMPLY TO FBC FIEL
 GAS. SEPARATE PLANS AND PERMIT REQUIRED.
 ADD TO NOTES.