Plan Review Notes For Permit 05070229 |
Permit Number |
05070229 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-26 00:00:00 | DENIED; | | 1.SEC.424.2.7.1 EQUIPMENT SLAB TO BE | | 4"THICK. SHOW ON PLAN | | 2.424.2.8.1 VALVESSHALL BE READLY | | ACCESSIBLE FOR MAINT. AND REMOVAL. FULL | | WAY VALVES SHALL BE INSTALLED. WHERE | | CHECK VALVES ARE USED THEY SHALL BEOF | | THE SWING OR VERTICAL CHECK PATTERNS. ( | | ADD TO NOTES) | | 3.WATER SUPPLY LOCAL ORD. #2853-95, | | BACKFLOW REQUIRED ON WATER SERVICES. | | (ADD TO NOTES) | | 4.PRESSURE TESTS. PER. MANUFACTURE | | RECOMMENDATIONS, NO AIR TEST SHALL BE | | APPROVED FOR PVC PIPE AND FITTINGS. (ADD | | TO NOTES) | | 5.FBC PLUMBING SEC.605.21 PURPLE PRIMER | | REQUIRED ON PVC PIPE AND FITTINGS. (ADD | | TO NOTES) | | 6.424.2.14.4 ALL WATER HEATER EQUIPMENT | | SHALL BE INSTALLED WITH FLANGES OR UNION | | CONNECTIONS ADJACENT TO HEATER. (ADD TO | | NOTES) | | 7.GAS PIPING SHALL COMPLY TO FBC FIEL | | GAS. SEPARATE PLANS AND PERMIT REQUIRED. | | ADD TO NOTES. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|