Plan Review Notes
Plan Review Notes For Permit 05070207
Permit Number 05070207
Review Stop E
Sequence Number 7
Notes
Date Text
2007-05-17 15:40:08** UNSAT **
  
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULES HAVE NOW
 REMOVED THE REQUIRED ARC FAULT PROTECTION FROM BREAKERS
 TO A/C UNITS.
 PLEASE CLARIFY THIS AS AFCI PROTECTION IS REQUIRED ON
 ALL 15/20AMP BRANCH CIRCUITS IN BEDROOM/SLEEPING
 ROOMS.
 PLEASE KNOW IF THIS IS INDEED A 2-POLE UNIT, PLEASE
 REVISE PANEL SCHEDULE TO INCLUDE THE 1/3 SPACES AND THE
 2/4 SPACES. ON EACH PANEL.
  
 2) NOTE: PLEASE SEE PREVIOUS PLANS WERE REDLINED AS
 RISER NOTE #2 INDICATES AN *EQUIPMENT GROUNDING
 CONDUCTOR* BEFORE THE FIRST MEANS OF DISCONNECT WHICH
 IS NOT PERMITTED. 250.6, 250.24.
 PLEASE REVISE AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  