Plan Review Notes
Plan Review Notes For Permit 05070207
Permit Number 05070207
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-05 00:00:00***UNSAT 2ND REVIEW *****
  
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NO, ALTHOUGH REPSONSE LTR
 MENTIONS THIS SHALL BE UNDER A SEPARATE
 PERMIT, THE PLANS DO NOT NOTE THIS.
 IF UNDER THIS PERMIT. PLEASE INCLUDE
 WIND LOADING FOR SITE LIGHTING POLES.
 PLEASE SEE THE WIND LOAD CALCS ARE
 REQUIRED AT THIS TIME AND SHALL BE
 REVIWED BY BLDG PLAN REVIEW.
  
 3)NOTE: NOTE #3 NO, PLEASE INCLUDE
 SIZING FOR ALL EXISTING SEC'S.
 215.5
 PLEASE SEE 240.4,310.16
 PLEASE SEE RESPONSE LTR MENTIONS, LOAD
 CALCUALTIONS PROVIDED, HOWEVER EXISTING
 SEC'S COULD NOT BE LOCATED.
  
 4)NOTE: NOTE#4
 ** MOTEL OCCUPANCY**
 PLEASE SUBMIT LOAD CALCULATIONS PER
 2002 NEC.
 PLEASE ALSO SEE LOAD CALCS FOR SERVICE
 ARE TO MEET 220.3,220.10,220.11 ETC.
 PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS
 WHICH ARE NOW SHOWN NEED TO BE SHOWN PER
 NEC.
 PLEASE INCLUDE ALL LOADS OF EXISTING AND
 NEW.
 215.5
  
 5)NOTE:NOTE #5 NO, PLEASE CORRELATE
 LOADS SHOWN ON PANEL PH WITH LOADS
 INDICATED ON PANEL SCHEDULES FOR UNITS.
 215.5
 PLEASE SEE LAODS FOR PANELS,P8,P9 AND
 P10 DO CORRELATE. (4.4, 4.6)
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE:NOTE # 7 NO, PLEASE SEE
 RESPONSE MENTIONS SEE REVISED E-1 AND
 E-4, HOWEVER E-1 INDICATES ARC FAULT FOR
 RECEPTS ONLY. PLEASE SEE "ALL OUTLETS"
 PER PLEASE SEE ARC FAULT PROTECTION
 WILL BE REQUIRED UNDER 2002 NEC 210.12
  
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 OK.
  
  
 10)NOTE: NOTE #10 OK, HOWEVER NO
 VERIFICATION OF SIZING CAN BE DONE, AS
 SEC'S ARE NOT SHOWN.PLEASE PROVIDE SIZE
 OF EXSITNG TAP/GUTTER BOX. ( LENGTH)?
 SIZE SHALL BE VERIFIED FOR NEW OR
 EXISTING SEC'S.
 366.6
  
 11)NOTE: PLEASE NOTE,, TYPE OF CONDUIT
 FOR FEEDERS TO UNITS IS NOT SHOWN, IF
 PVC AND SCH 80, PLEASE SEE CONDUIT FILL
 WILL EXCEED PERMITTED FILL FROM TABLES
 IN CHAPTER 9. THIS IS ONLY A NOTE:
  
 PLEASE BE SURE TO SEE ANY POSSIBEL
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE BE SURE TO SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]