2005-12-05 00:00:00 | ***UNSAT 2ND REVIEW ***** |
| |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| |
| 1)NOTE: NOTE #1 OK. |
| |
| 2)NOTE: NO, ALTHOUGH REPSONSE LTR |
| MENTIONS THIS SHALL BE UNDER A SEPARATE |
| PERMIT, THE PLANS DO NOT NOTE THIS. |
| IF UNDER THIS PERMIT. PLEASE INCLUDE |
| WIND LOADING FOR SITE LIGHTING POLES. |
| PLEASE SEE THE WIND LOAD CALCS ARE |
| REQUIRED AT THIS TIME AND SHALL BE |
| REVIWED BY BLDG PLAN REVIEW. |
| |
| 3)NOTE: NOTE #3 NO, PLEASE INCLUDE |
| SIZING FOR ALL EXISTING SEC'S. |
| 215.5 |
| PLEASE SEE 240.4,310.16 |
| PLEASE SEE RESPONSE LTR MENTIONS, LOAD |
| CALCUALTIONS PROVIDED, HOWEVER EXISTING |
| SEC'S COULD NOT BE LOCATED. |
| |
| 4)NOTE: NOTE#4 |
| ** MOTEL OCCUPANCY** |
| PLEASE SUBMIT LOAD CALCULATIONS PER |
| 2002 NEC. |
| PLEASE ALSO SEE LOAD CALCS FOR SERVICE |
| ARE TO MEET 220.3,220.10,220.11 ETC. |
| PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS |
| WHICH ARE NOW SHOWN NEED TO BE SHOWN PER |
| NEC. |
| PLEASE INCLUDE ALL LOADS OF EXISTING AND |
| NEW. |
| 215.5 |
| |
| 5)NOTE:NOTE #5 NO, PLEASE CORRELATE |
| LOADS SHOWN ON PANEL PH WITH LOADS |
| INDICATED ON PANEL SCHEDULES FOR UNITS. |
| 215.5 |
| PLEASE SEE LAODS FOR PANELS,P8,P9 AND |
| P10 DO CORRELATE. (4.4, 4.6) |
| |
| 6)NOTE: NOTE #6 OK. |
| |
| 7)NOTE:NOTE # 7 NO, PLEASE SEE |
| RESPONSE MENTIONS SEE REVISED E-1 AND |
| E-4, HOWEVER E-1 INDICATES ARC FAULT FOR |
| RECEPTS ONLY. PLEASE SEE "ALL OUTLETS" |
| PER PLEASE SEE ARC FAULT PROTECTION |
| WILL BE REQUIRED UNDER 2002 NEC 210.12 |
| |
| |
| 8)NOTE: NOTE #8 OK. |
| |
| 9)NOTE: NOTE #9 OK. |
| |
| |
| 10)NOTE: NOTE #10 OK, HOWEVER NO |
| VERIFICATION OF SIZING CAN BE DONE, AS |
| SEC'S ARE NOT SHOWN.PLEASE PROVIDE SIZE |
| OF EXSITNG TAP/GUTTER BOX. ( LENGTH)? |
| SIZE SHALL BE VERIFIED FOR NEW OR |
| EXISTING SEC'S. |
| 366.6 |
| |
| 11)NOTE: PLEASE NOTE,, TYPE OF CONDUIT |
| FOR FEEDERS TO UNITS IS NOT SHOWN, IF |
| PVC AND SCH 80, PLEASE SEE CONDUIT FILL |
| WILL EXCEED PERMITTED FILL FROM TABLES |
| IN CHAPTER 9. THIS IS ONLY A NOTE: |
| |
| PLEASE BE SURE TO SEE ANY POSSIBEL |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT ELECTRICAL PLANS. |
| |
| PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| PLEASE BE SURE TO SUBMIT ONE COPY OF |
| OLD/VOIDED SHEETS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |