2005-07-27 00:00:00DENIED:
 1.PLAN SHEET M-1 EXHAUST DUCTS
 PENETRATING RATED PARTITIONS SHALL
 COMPLY WITH 2001 FBC(M)607.1.3 #3 ITEMS
 1 THROUGH 4 OR FIRE DAMPERS WILL BE
 REQUIRED.
  
 2.PLEASE PROVIDE ADDTIONAL INFORMATION
 FOR THE LAUNDRY ROOM.PLAN SHEET P-3
 INDICATES GAS WATER HEATER AND DRYERS.
 PROVIDE COMBUSTION AIR CALCULATIONS.
  
 3.INDICATE TERMINATION OF THE DRYER
 EXHAUST.
  
 4.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA/INSTALLATION INSTRUCTIONS
 FOR THE A/C PACKAGE UNITS, WASHERS,
 DRYERS & WATER HEATER.
  