Plan Review Notes For Permit 05070207 |
Permit Number |
05070207 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-27 00:00:00 | DENIED: | | 1.PLAN SHEET M-1 EXHAUST DUCTS | | PENETRATING RATED PARTITIONS SHALL | | COMPLY WITH 2001 FBC(M)607.1.3 #3 ITEMS | | 1 THROUGH 4 OR FIRE DAMPERS WILL BE | | REQUIRED. | | | | 2.PLEASE PROVIDE ADDTIONAL INFORMATION | | FOR THE LAUNDRY ROOM.PLAN SHEET P-3 | | INDICATES GAS WATER HEATER AND DRYERS. | | PROVIDE COMBUSTION AIR CALCULATIONS. | | | | 3.INDICATE TERMINATION OF THE DRYER | | EXHAUST. | | | | 4.PLEASE PROVIDE MANUFACTURER | | SUBMITTAL DATA/INSTALLATION INSTRUCTIONS | | FOR THE A/C PACKAGE UNITS, WASHERS, | | DRYERS & WATER HEATER. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|