2005-07-22 00:00:00 | ************* UNSAT *********** |
| |
| 1)NOTE: PLEASE INCLUDE ALL INFORMATION |
| ON TITLE BLOCK AS REQUIRED UNDER FAC |
| 61G15-23.002, PLEASE SEE MISSING PRINTED |
| NAME. |
| |
| 2)NOTE: PLEASE INCLUDE WINDING LOADING |
| FOR SITE LIGHTING POLES. |
| PLEASE SEE THE WIND LOAD CALCS ARE |
| REQUIRED AT THIS TIME AND SHALL BE |
| REVIWED BY BLDG PLAN REVIEW. |
| |
| 3)NOTE: PLEASE INCLUDE SIZING FOR ALL |
| EXISTING SEC'S. |
| 215.5 |
| PLEASE SEE 240.4,310.16 |
| |
| 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| PER 2002 NEC. PLEASE SEE HOUSE LOADS ARE |
| SHOWN BEING DERATED WITH DWELLING UNIT |
| LOADS WHICH IS NOT PERMITTED. |
| PLEASE ALSO SEE LOAD CALCS FOR SERVICE |
| ARE TO MEET 220.3,220.10,220.11 ETC. |
| PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS |
| ARE NOT SHOWN AND/OR ARE NOT INCLUDED IN |
| SERVICELOAD CALCS. |
| PLEASE INCLUDE ALL LOADS OF EXISTING AND |
| NEW. |
| 215.5 |
| |
| 5)NOTE: PLEASE CORRELATE LOADS SHOWN ON |
| PANEL PH WITH LOADS INDICATED ON PANEL |
| SCHEDULES FOR UNITS. |
| 215.5 |
| PLEASE SEE LAODS FOR PANELS,P8,P9 AND |
| P10 DO CORRELATE. |
| |
| 6)NOTE: PLEASE SEE MIN CIRCUIT FOR BATHS |
| ARE TO MEET 210.52,210.11C3, MUST BE 20A |
| AND #12. |
| |
| 7)NOTE: PLEASE SEE ARC FAULT PROTECTION |
| WILL BE REQUIRED UNDER 2002 NEC 210.12 |
| PLEASE SEE "ALL OUTLETS" , SD'S, LTS, |
| FANS, RECEPTS ETC ARE TO AHVE ARC FAULT |
| PROTECTED CIRCUITS. |
| |
| 8)NOTE: PLEASE A MIN OF 1500 VA SHALL |
| APPLY TO LAUNDRY CIRCUIT. |
| PLEASE SEE 210.11C2, 220.16B |
| |
| 9)NOTE: PLEASE SEE 250.6,250.24, |
| EQUIPMENT GROUNDING CONDUCTORS SHALL NOT |
| BE INSTALLED UNTIL AFTER THE FIRST MEANS |
| OF DISCONNECT. |
| PLEASE SEE #3 EG SHOWN FROM GUTTER TO |
| NEW METER/ MAIN. |
| |
| 10)NOTE: PLEASE PROVIDE SIZE OF EXSITNG |
| TAP/GUTTER BOX. |
| SIZE SHALL BE VERIFIED FOR NEW OR |
| EXISTING SEC'S. |
| 366.6 |
| |
| PLEASE BE SURE TO SEE ANY POSSIBEL |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT ELECTRICAL PLANS. |
| |
| PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| PLEASE BE SURE TO SUBMIT ONE COPY OF |
| OLD/VOIDED SHEETS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |