Plan Review Notes
Plan Review Notes For Permit 05070207
Permit Number 05070207
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-22 00:00:00************* UNSAT ***********
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002, PLEASE SEE MISSING PRINTED
 NAME.
  
 2)NOTE: PLEASE INCLUDE WINDING LOADING
 FOR SITE LIGHTING POLES.
 PLEASE SEE THE WIND LOAD CALCS ARE
 REQUIRED AT THIS TIME AND SHALL BE
 REVIWED BY BLDG PLAN REVIEW.
  
 3)NOTE: PLEASE INCLUDE SIZING FOR ALL
 EXISTING SEC'S.
 215.5
 PLEASE SEE 240.4,310.16
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 2002 NEC. PLEASE SEE HOUSE LOADS ARE
 SHOWN BEING DERATED WITH DWELLING UNIT
 LOADS WHICH IS NOT PERMITTED.
 PLEASE ALSO SEE LOAD CALCS FOR SERVICE
 ARE TO MEET 220.3,220.10,220.11 ETC.
 PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS
 ARE NOT SHOWN AND/OR ARE NOT INCLUDED IN
 SERVICELOAD CALCS.
 PLEASE INCLUDE ALL LOADS OF EXISTING AND
 NEW.
 215.5
  
 5)NOTE: PLEASE CORRELATE LOADS SHOWN ON
 PANEL PH WITH LOADS INDICATED ON PANEL
 SCHEDULES FOR UNITS.
 215.5
 PLEASE SEE LAODS FOR PANELS,P8,P9 AND
 P10 DO CORRELATE.
  
 6)NOTE: PLEASE SEE MIN CIRCUIT FOR BATHS
 ARE TO MEET 210.52,210.11C3, MUST BE 20A
 AND #12.
  
 7)NOTE: PLEASE SEE ARC FAULT PROTECTION
 WILL BE REQUIRED UNDER 2002 NEC 210.12
 PLEASE SEE "ALL OUTLETS" , SD'S, LTS,
 FANS, RECEPTS ETC ARE TO AHVE ARC FAULT
 PROTECTED CIRCUITS.
  
 8)NOTE: PLEASE A MIN OF 1500 VA SHALL
 APPLY TO LAUNDRY CIRCUIT.
 PLEASE SEE 210.11C2, 220.16B
  
 9)NOTE: PLEASE SEE 250.6,250.24,
 EQUIPMENT GROUNDING CONDUCTORS SHALL NOT
 BE INSTALLED UNTIL AFTER THE FIRST MEANS
 OF DISCONNECT.
 PLEASE SEE #3 EG SHOWN FROM GUTTER TO
 NEW METER/ MAIN.
  
 10)NOTE: PLEASE PROVIDE SIZE OF EXSITNG
 TAP/GUTTER BOX.
 SIZE SHALL BE VERIFIED FOR NEW OR
 EXISTING SEC'S.
 366.6
  
 PLEASE BE SURE TO SEE ANY POSSIBEL
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE BE SURE TO SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  