Plan Review Notes For Permit 05070207
Permit Number 05070207
Review Stop B
Sequence Number 1
Notes
Date Text
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070207
 ADD: 3712 BROADWAY
 CONT: K& M COMMERCIAL CONSTRUCTION
 TEL: (561)248-9648
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PERMIT APPLICATION INDICATES WORK IS
 TO BE COMPLETED AT 3712 BROADWAY. WORK
 TO BE COMPLETED AT 3702 BROADWAY.
 CORRECT APPLICATION AND PROPERTY CONTROL
 NUMBER.
  
 2) PROVIDE A SURVEY FOR 3702 BROADWAY.
 THE NORTH SIDE OF BUILDING MAY HAVE
 TABLE 600 ISSUES.
  
 3)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 4)3401.2.2.1 IF THE OCCUPANCY
 CLASSIFICATION OR OCCUPANCY
 SUBCLASSIFICATIONS OF ANY EXISTING
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL
 AND PLUMBING SYSTEMS SHALL BE MADE TO
 CONFORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING
 OFFICIAL.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 7) 1203.1.3 ATTICS NOT USED FOR
 HABITATIONAL PURPOSES SHALL HAVE
 PROVISIONS FOR THE EMISSION OF EXCESS
 HEAT.
  
 8)2309.6 ACCESS TO ATTIC SPACE. ATTIC
 SPACES SHALL BE PROVIDED WITH AN
 INTERIOR ACCESS OPENING NOT LESS THAN
 20X36 INCHES (508X914 MM).ACCESS
 OPENING SHALL BE ACCESSIBLE AND PROVIDED
 WITH A LID OR DEVICE THAT MAY BE
 EASILY REMOVED OR OPERATED.WHEN
 MECHANICAL EQUIPMENT IS TO BE INSTALLED
 IN THE ATTIC, IT SHALL BE INSTALLED IN
 ACCORDANCE WITH ?M306.3 OF FLORIDA
 BUILDING CODE, MECHANICAL.ACCESS IS
 NOT REQUIRED WHEN THE CLEAR HEIGHT
 OF THE ATTIC SPACE, MEASURED AT THE ROOF
 PEAK, IS LESS THAN 24 INCHES (610
 MM).
  
 9) PROVIDE CALCULATIONS:1203.1.4 EXCEPT
 AS OTHERWISE PROVIDED HEREIN, REQUIRED
 WINDOWS SHALLHAVE GLAZED OPENINGS OF
 CLEAR GLASS OF AREA NOT LESS THAN 8% OF
 THE FLOOR AREA OF THE ROOM SERVED.
  
 10) DOORS SEE LABEL "C": 11-4.13.5 CLEAR
 WIDTH. DOORWAYS SHALL HAVE A MINIMUM
 CLEAR OPENING OF32 INCHES (815 MM)
 WITH THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THEFACE OF THE DOOR AND THE
 OPPOSITE STOP (SEE FIGURE 11-24(A),
 FIGURE 11-24(B), FIGURE 11-24(C), AND
 FIGURE 11-24(D)).OPENINGSMORE THAN
 24 INCHES (610 MM) IN DEPTH SHALL COMPLY
 WITH 11-4.2.1 AND 11-4.3.3 (SEE FIGURE
 11-24(E)).
  
 11)11-9.1.2 ACCESSIBLE UNITS, SLEEPING
 ROOMS, AND SUITES. ACCESSIBLESLEEPING
 ROOMS OR SUITES THAT COMPLY WITH THE
 REQUIREMENTS OF ?11-9.2.1TO ?11-9.2.2
 (REQUIREMENTS FOR ACCESSIBLE UNITS,
 SLEEPING ROOMS, ANDSUITES) SHALL BE
 PROVIDED IN CONFORMANCE WITH THE TABLE
 BELOW.INADDITION, IN HOTELS, OF 50
 OR MORE SLEEPING ROOMS OR SUITES,
 ADDITIONALACCESSIBLE SLEEPING ROOMS
 OR SUITES THAT INCLUDE A ROLL-IN SHOWER
 SHALL ALSO BE PROVIDED IN CONFORMANCE
 WITH THE TABLE BELOW.SUCH
 ACCOMMODATIONS SHALL COMPLY WITH THE
 REQUIREMENTS OF ?11-9.2, ?11-4.21,
 AND FIGURE 11-57(A) OR FIGURE 11-57(B).
  
 12) PLANS DO NOT INDICATE FLOOR LEVEL ON
 THE EXTERIOR OF THE EXTERIOR DOORS,
 INDICATE GRADE IN RELATIONSHIP TO FINISH
 FLOOR LEVEL. 11-4.3.2(3) AT LEAST ONE
 ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS AND WITH ALL ACCESSIBLE
 DWELLING UNITS WITHIN THE BUILDING OR
 FACILITY.
  
 13) 11-4.6.1 MINIMUM NUMBER. PARKING
 SPACES REQUIRED TO BE ACCESSIBLE BY
 11-4.1 SHALL COMPLY WITH ?11-4.6.2
 THROUGH ?11-4.6.5.PASSENGER LOADING
 ZONES REQUIRED TO BE ACCESSIBLE BY
 11-4.1 SHALL COMPLY WITH 11-4.6.5 AND
 11-4.6.6.
  
 14) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 15)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) DOORS
 B) WINDOWS
  
 15) BATHROOMS:1204.2 SURROUNDING
 MATERIALS; THE WALLS & FLOORS OF ALL
 PUBLIC REST- ROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIALS TO A HEIGTH OF
 4'-0" ABOVE THE FLOOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  