Plan Review Notes
Plan Review Notes For Permit 05070171
Permit Number 05070171
Review Stop E
Sequence Number 7
Notes
Date Text
2007-08-06 15:38:26** DENIED **
  
  
 1) NOTE: PLEASE SEE THE REVISED PLANS SUBMITTED NEED TO
 CONTAIN THE REVISED AS IMPLIED ON THE REVISION COVER
 SHEET AS FILED BY CONTRACTOR.
 PLEASE SEE THIS SHEET MENTIONS REVISED THE LIGHTING AND
 NUMBER OF FIXTURES YET NO INFORMATION COULD BE LOCATED
 FOR REVISED LOADS PER CHAPTER 13. 103.101, 13-415.2
 PLEASE BE SURE TO REVISE ENERGY CALCULATIONS FOR
 INCREASED LIGHTING.
  
 2) NOTE: PLEASE REVISE PANEL SCHEDULE TO INDICATE ALL
 CIRCUITS TO THE SPECIFIC AREAS/ROOMS IN WHICH THEY
 FEED. PLEASE SEE THE USE OF *LIGHTING* OR *RECEPTACLES*
 IS NOT ACCEPTABLE PER 408.4.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  