Plan Review Notes For Permit 05070171 |
Permit Number |
05070171 |
|
Review Stop |
E |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2007-08-06 15:38:26 | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE THE REVISED PLANS SUBMITTED NEED TO | | CONTAIN THE REVISED AS IMPLIED ON THE REVISION COVER | | SHEET AS FILED BY CONTRACTOR. | | PLEASE SEE THIS SHEET MENTIONS REVISED THE LIGHTING AND | | NUMBER OF FIXTURES YET NO INFORMATION COULD BE LOCATED | | FOR REVISED LOADS PER CHAPTER 13. 103.101, 13-415.2 | | PLEASE BE SURE TO REVISE ENERGY CALCULATIONS FOR | | INCREASED LIGHTING. | | | | 2) NOTE: PLEASE REVISE PANEL SCHEDULE TO INDICATE ALL | | CIRCUITS TO THE SPECIFIC AREAS/ROOMS IN WHICH THEY | | FEED. PLEASE SEE THE USE OF *LIGHTING* OR *RECEPTACLES* | | IS NOT ACCEPTABLE PER 408.4. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|