Plan Review Notes For Permit 05070171 |
Permit Number |
05070171 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-01-24 00:00:00 | *********** NOTES REDLINED *********** | | | | | | | | 1)NOTE: PLEASE SEE STAIRWAY IS REQUIRED | | TO HAVE A BATTERY BACK UP LIGHT FIXTURE | | AS REQUIRED UNDER LS 101 7.8,7.9.2.1 | | | | ** PLEASE SEE A MIN OF 10FT CANDLES(108 | | LUX)IS REQUIRED UNDER NORMAL POWER AND | | 1FT CANDLE (10.8 LUX) UNDER | | EM.7.9.2.2,7.8.1.3 | | |
|