2006-01-24 00:00:00*********** NOTES REDLINED ***********
  
  
  
 1)NOTE: PLEASE SEE STAIRWAY IS REQUIRED
 TO HAVE A BATTERY BACK UP LIGHT FIXTURE
 AS REQUIRED UNDER LS 101 7.8,7.9.2.1
  
 ** PLEASE SEE A MIN OF 10FT CANDLES(108
 LUX)IS REQUIRED UNDER NORMAL POWER AND
 1FT CANDLE (10.8 LUX) UNDER
 EM.7.9.2.2,7.8.1.3
  