Plan Review Notes For Permit 05070171 |
Permit Number |
05070171 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-12-02 00:00:00 | PROVISO: | | 1.PLAN SHEET ME.2 GENERAL MECHANICAL | | NOTE #9 INDICATES OUTSIDE EQUIPMENT TO | | BE SECURED TO WITHSTAND 120 MPH WINDS. | | THIS SHOULD READ 140 MPH. | | | | 2.PLEASE REVISE PLAN TO INDICATE | | LOCATION OF THE CONDENSING UNITS. | | SHOULD UNITS BE LOCATED ON THE ROOF, | | PLEASE SHOW COMPLIANCE WITH 2001 FBC | | 1511.7 FOR PROPER CLEARANCE BETWEEN THE | | ROOF SURFACE AND THE BOTTOM OF THE | | SUPPORT RAIL OF THE STAND.IF UNITS ARE | | LOCATED AT GROUND LEVEL SHOW COMPLIANCE | | WITH 2001 FMC 301.13 FOR ANCHORING. | | | | PLEASEREVISE PLANS TO REFLECT THE | | ABOVE INFORMATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|