Plan Review Notes
Plan Review Notes For Permit 05070171
Permit Number 05070171
Review Stop M
Sequence Number 2
Notes
Date Text
2005-12-02 00:00:00PROVISO:
 1.PLAN SHEET ME.2 GENERAL MECHANICAL
 NOTE #9 INDICATES OUTSIDE EQUIPMENT TO
 BE SECURED TO WITHSTAND 120 MPH WINDS.
 THIS SHOULD READ 140 MPH.
  
 2.PLEASE REVISE PLAN TO INDICATE
 LOCATION OF THE CONDENSING UNITS.
 SHOULD UNITS BE LOCATED ON THE ROOF,
 PLEASE SHOW COMPLIANCE WITH 2001 FBC
 1511.7 FOR PROPER CLEARANCE BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL OF THE STAND.IF UNITS ARE
 LOCATED AT GROUND LEVEL SHOW COMPLIANCE
 WITH 2001 FMC 301.13 FOR ANCHORING.
  
 PLEASEREVISE PLANS TO REFLECT THE
 ABOVE INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.