2005-08-08 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT 3.1 MEZZANINE FLOOR PLAN. PRIVATE |
| BATHROOM SHALL BE ADAPTABLE. INDICATE |
| BACKING FOR ALL GRAB BARS FOR TOILET & |
| SHOWER, 5' TURNING AREA. WATER CLOSET |
| SHALL BE 18" FROM WALL TO CENTERLINE OF |
| FIXTURE. (SEE SECTION 11-4.16.4). |
| SECTION 11-4.1.3(11). |
| 2. SINKS ON FIRST FOOR AND ON MEZZANINE |
| LEVEL SHALL BE ACCESSIBLE. PLEASE SUBMIT |
| A DETAIL FOR SINKS COMPLYING WITH THE |
| FOLLOWING: |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE. - |
| FORWARD APPROACH REQUIRED AND SHALL |
| EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| SINK. |
| E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| F. 11-4.24.7 FAUCETS. |
| 3. SHT 10.1 DRINKING FOUNTAIN DETAIL, |
| SHOW COMPLIANCE WITH 11-15.4.1.3(10)(A) |
| PROVISIONS FOR THOSE WHO HAVE DIFFICULTY |
| BENDING OR STOOPING. |
| 4. SHTS ME.1 & ME.2 IF THE DESIGN |
| PROFESSIONAL IS AN ENGINEER THEN HE/SHE |
| SHALL AFFIX HIS/HER OFFICIAL SEAL TO |
| SAID DRAWINGS AS REQUIRED BY FLORIDA |
| STATUTES. SECTION 104.2.2. |
| 5. SHT ME.1 SANITARY RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| MEET CODE REQUIREMENTS. CORRECT THE |
| FOLLOWING: |
| A. THE SNACK SINK SHALL NOT CONNECT TO |
| THE WET VENT FOR THE BATHROOM FIXTURES. |
| THE SINK SHALL DISCHARGE DOWNSTREAM OF |
| THE BATHROOM FIXTURES. SECTION 909.1. |
| B. THE BATHROOM FIXTURES OF THE |
| MEZZANINE SHALL NOT DRAIN PAST THE VENT |
| FOR THE 1ST FLOOR FIXTURES. SECTION |
| 908.3. |
| C. THE MEZZANINE LEVEL SINK IN THE OPEN |
| OFFICE (521) IS NOT SHOWN ON THE SANT. |
| RISER DIAGRAM. SECTION 104.2.1. |
| D. MEZZANINE PIPING DOES NOT REFLECT |
| THE FLOOR PLAN. RISER SHOWS THE LAV AND |
| SHOWER ON THE SAME SIDE OF THE ROOM. |
| SECTION 104.2.1. |
| 6. SUBMIT A WATER RISER DIAGRAM IN |
| ISOMETRIC FORM. SECTION 104.3.1.1. |
| |