Plan Review Notes For Permit 05070171 |
Permit Number |
05070171 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-26 00:00:00 | DENIED: | | 1.PLAN SHEET ME-1 IT APPEARS THE | | EXISTING 6" OA DUCT IS TIED INTO AHU #2 | | ONLY.THE OA CALCULATION GIVEN ON PLAN | | SHEET ME-2 ONLY GIVES OA CALCS FOR | | SYSTEM #1.PLEASE CLARIFY. | | | | 2.PLEASE CLARIFY EXHAUAST FROM THE 1ST | | FLOOR UNISEX BATHROOM AS WELL AS THE 2ND | | FLOOR PRIVATE BATHROOM. | | | | 3.PLEASE CLARIFY VENTILATION FROM THE | | 1ST FLOOR STORAGE & LOADING AREAS. | | | | 4.PLEASE NOTE, DUCTS PENETRATING THE | | RATED WALL FROM OFFICE #507 INTO OFFICE | | #501, THESE DUCTS WILL NOT REQUIRE FIRE | | DAMPERS AS LONG AS IT MEETS THE | | REQUIREMENTS OF 2001 FBC(M)607.1.3 ITEM | | #3 1 THROUGH 4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|