2005-07-12 00:00:00 | ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE SEE 310.16,240.4 FOR MIN |
| SIZING FOR FEEDERS FROM 200A MAIN |
| DISCONNECT TO INSIDE PANEL "A". PLEASE |
| SEE MAIN IS SHOWN W/ 200A OCP ON |
| CONDUCTORS ONLY RATED FOR 150A'S. |
| |
| 2)NOTE: PLEASE SEE 700.12E FOR |
| CIRCUITING OF EM/EXT LTS. THE BRANCH |
| CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT |
| SERVING THE NORMAL LIGHTING IN THE AREA |
| AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. |
| |
| 3)NOTE: PLEASE SEE THE ENGINEER AS SHOWN |
| ON TITLE BLOCK RESPONSIBLE FOR DESIGN |
| AND/OR PLANS, SHALL SIGN, DATE AND SEAL |
| PLANS AS REQUIRED UNDER FS 471.025 |
| PLEASE SEE THIS IS REQUIRED OF ALL SAID |
| SHEETS WHEATHER OR NOT COMMENT IS MADE |
| BY OTHER TRADES. |
| |
| PLEASE BE SURE TO REMOVE ANY OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. ONE COPY OF OLD SHEETS SHOULD |
| BE SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESTITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |