1 |
|
Notes |
Date |
Text |
2005-07-30 00:00:00 | DENIED; | | 1. DELETE PLUMBING NOTE #1. FBC PLUMBING | | 701.2. | | 2.SANITARY RISER DIAGRAM IS NOT TO CODE. | | 2ND FLOOR BATH CANNOT DUMP INTO 1ST | | FLOOR WET VENT FOR DOWN STAIRS BATHROOM. | | W/M VENT MUST EXTEND 6" ABOVE THE | | HIGHEST FIXTURE ON SECOND FLOOR. | | 3.P-1 WHAT IS 3" LINE ON SECOND FLOOR | | (MARKED IN YELLOW) FOR? | | 4.DELETE REFORENCE TO AIR CHAMBERS AND | | INSTALL SHOCK ARRESTORS PER SEC. 604.9. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|