2005-08-01 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05070147 |
| ADD: 615 4TH ST |
| CONT: KENACO |
| TEL: (561)315-5070 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| NOTE: PERMIT APPLICATION DESSCRIPTION |
| INTERIOR REPAIRS BUT NOTHING ON THE |
| INTERIOR INDICATES A CHANGE, ONLY |
| REVIEWED FOR NEW WINDOWS, EXTERIOR DOORS |
| & STORM SHUTTERS. |
| |
| 1)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 2) BEDROOM EGRESS WINDOW VENTS ARE LESS |
| THAN 5'-0" SQ FT OPENING. |
| 2001 FL BLD CODE, 1005.4: |
| PROVIDE EMERGENCY EGRESS WINDOWS IN |
| SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| OPENING HEIGTH OF 24" AND NET CLEAR |
| OPENING WIDTH OF 20" AND A NET CLEAR |
| OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| OPENINGS ARE PERMITTED TO HAVE A NET |
| CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| SHALL NOT BE MORE THAN 44 " ABOVE THE |
| FINISH FLOOR. |
| |
| 3)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) MULLIONS WINDOWS |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |