Plan Review Notes
Plan Review Notes For Permit 05070083
Permit Number 05070083
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070083
 ADD: 6118 WILDCAT RUN
 CONT:O/B FAKHARI, MOHAMMAD
 TEL: (561)310-7460
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PERMIT APPLICATION DOESN'T INDICATE
 WHAT MATERIALS THE EXISTING FIREPLACE
 NOR CHIMNEY IS MADE OF. IF THE FIREPLACE
 AND OR CHIMNEY IS FACTORY BUILT, IT HAS
 TO CONFORM TO THOUGHS SPECIFICATIONS
 UNDER WHICH IT WAS BUILT AND TESTED.
  
 2806.1.1 FACTORY-BUILT FIREPLACES SHALL
 BE LISTED AND SHALL BE INSTALLED
 IN ACCORDANCE WITH THE CONDITIONS OF
 THE LISTING.
  
 2806.1.2 FACTORY-BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH
 AND MEET THE REQUIREMENTS OF UL 127.
  
 2804.4.1 FACTORY-BUILT CHIMNEYS SHALL BE
 LISTED AND SHALL BE INSTALLED
 IN ACCORDANCE WITH THE CONDITIONS OF
 THE LISTING, AND THE MANUFACTURER'S
 INSTRUCTIONS.NOTHING CONTAINED IN
 THIS CODE SHALL BE CONSTRUED AS
 PROHIBITING THE USE OF INSULATED
 SUSPENDED FACTORY-BUILT CHIMNEYS
 PROVIDED SUCH ASSEMBLIES HAVE BEEN
 TESTED AND APPROVED BY A RECOGNIZED
 LABORATORY FOR THE USE INTENDED AND
 ARE INSTALLED IN ACCORDANCE WITH
 THEIR APPROVAL.
  
  
 ALTERING THE END CAPS AND THE DISPERSION
 OF SMOKE AND HEAT WITH THE DRAWINGS
 BY P.E. GORDON BUCK IS NOT RECOGNIZED
 NOR TESTED BY UL 127.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  