2005-07-31 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05070083 |
| ADD: 6118 WILDCAT RUN |
| CONT:O/B FAKHARI, MOHAMMAD |
| TEL: (561)310-7460 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| THE PERMIT APPLICATION DOESN'T INDICATE |
| WHAT MATERIALS THE EXISTING FIREPLACE |
| NOR CHIMNEY IS MADE OF. IF THE FIREPLACE |
| AND OR CHIMNEY IS FACTORY BUILT, IT HAS |
| TO CONFORM TO THOUGHS SPECIFICATIONS |
| UNDER WHICH IT WAS BUILT AND TESTED. |
| |
| 2806.1.1 FACTORY-BUILT FIREPLACES SHALL |
| BE LISTED AND SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE CONDITIONS OF |
| THE LISTING. |
| |
| 2806.1.2 FACTORY-BUILT FIREPLACES |
| SHALL BE TESTED IN ACCORDANCE WITH |
| AND MEET THE REQUIREMENTS OF UL 127. |
| |
| 2804.4.1 FACTORY-BUILT CHIMNEYS SHALL BE |
| LISTED AND SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE CONDITIONS OF |
| THE LISTING, AND THE MANUFACTURER'S |
| INSTRUCTIONS.NOTHING CONTAINED IN |
| THIS CODE SHALL BE CONSTRUED AS |
| PROHIBITING THE USE OF INSULATED |
| SUSPENDED FACTORY-BUILT CHIMNEYS |
| PROVIDED SUCH ASSEMBLIES HAVE BEEN |
| TESTED AND APPROVED BY A RECOGNIZED |
| LABORATORY FOR THE USE INTENDED AND |
| ARE INSTALLED IN ACCORDANCE WITH |
| THEIR APPROVAL. |
| |
| |
| ALTERING THE END CAPS AND THE DISPERSION |
| OF SMOKE AND HEAT WITH THE DRAWINGS |
| BY P.E. GORDON BUCK IS NOT RECOGNIZED |
| NOR TESTED BY UL 127. |