Plan Review Notes
Plan Review Notes For Permit 05070004
Permit Number 05070004
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-15 00:00:00********** UNSAT ******************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 NO ONLY RECEPTS WITHIN 6FT OF SINK AS
 NOTED ON PLANS.
 THAT CODE CHANGED FROM THE 1993 TO 1996
 NEC.
 ALL MUST HAVE GFI PROTECTION.
  
 3)NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 4)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 8-1.4.2
  
 6)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE NUMEROUS RECEPTS MISSING.
 PLEASE ALSO SEE SOME RECEPTS WHICH
 APPEAR TO BE SHOWN OUTSIDE OF WALLS AND
 OUTSIDE HOUSE?
  
 7)NOTE: PLEASE SEE 220V OUTLET WHICH IS
 SHOWN IN REAR KITCHEN WHICH IS NOT
 LISTEDON PANEL SCHEDULE OR LOAD
 CALCULATIONS.?
 215.5
  
 8)NOTE: PLEASE SEE PLANS INDICATE
 STACKABLE WASHER/DRYER UNITS, HOWEVER
 PANEL SCHEDULES SHOW INDIVIDUAL UNITS??
 PLEASE CORRELATE.
 215.5
  
 9)NOTE: PLEASE SEE PANEL SCHEDULES AND
 PLANS INDICATE MULTIPLE A/C SYSTEMS,
 HOWEVER ONLY ONE IS FIGURED IN LOADS
 CALCULATIONS.
 220.31
  
 10)NOTE: PLEASE 424.3 FOR MIN OCP FOR
 AHU'S. 125%
  
 11)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 TWO CIRCUITS FOR GEN LIGHTING WHICH
 SHOWS LOADS EXCEEDING BRANCH CIRCUIT
 RATING AND RATING OF AWG.
 240.4,310.16,220.3 ETC
 4AND 5 KW ON 15A CIRCUIT(S).
  
 12)NOTE: PLEASE LIST ALL ARC FAULT
 PROTECTED CIRCUITS PER 2002 NEC 210.12.
 THESE ARE BE LISTED ON PANEL SCHEDULE.
 215.5
  
 13)NOTE: PLEASE SEE MISSING CONDUCTORS
 FROM METER TO MAIN DISCONNECT AND MAIN
 DISC TO PANEL.
 215.5,310.15, 240.4.
 PLEASE ALSO SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISCONNECT
 TO PANEL.250.24,250.110,250.122
  
 14)NOTE: PLEASE SE GARAGE DOOR OPENER
 SHOWN ON PLANS, HOWEVER NOT LISTED ON
 PANEL SCHEDULE OR LOAD CALCS?
 220.31, 215.5
  
 15)NOTE: PLEASE KNOW, PLANS WHICH
 CONTAIN A TITLE BLOCK FROM AN ENGINEER
 OR ARCHITECT MUST BE SIGNED, DATED AND
 SEALED BY SAID ENGINEER OR ARCHITECT.
 FS 471.025,481.221
  
 16)NOTE: PLEASE SEE MISSING HALL RECEPT
 AS REQUIRED PER 210.52H
  
 17)NOTE: PLEASE SEE TWO RANGES/STOVES
 BEING SHOWN ON PLANS, HOWEVER ONLY ONE
 IS SHOWN ON PANEL SCHEDULE/LOAD
 CALCULATIONS.
 215.5
  
 18)NOTE: PLEASE SEE ZONING COMMENTS
 PERTAINING TO SECOND KITCHEN NOT BEING
 PERMITTED.
 THIS WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE KNOW, DUE TO THE EXTENT OF
 ELECTRICAL COMMENTS ETC, ONE COPY OF
 SAID ELECTRICAL PLANS SHALL BE RETAINED
 FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
2005-07-14 00:00:00IN ELEC FOR REVIEW.