2005-07-21 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE DESIGN PRESSURES ACCORDING TO
 THE BUILDING GEOMETRICAL SHAPE, HEIGHT,
 OPEN OR ENCLOSED BUILDING, EXPOSURE
 CATEGORY, TRIBUTARY AREA AND ZONE
 LOCATION AS REQUIRED BY ASCE 7-98.
 PROVIDE ENGINEERED CALCULATIONS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 2- ENGINEERED WIND LOAD TABLE NEEDS TO
 BE SIGNED AND SEALED BY THE ENGINEER WHO
 PREPARED IT AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 TABLE IS GENERIC. ENGINEER TO PROVIDE
 CALCULATIONS FOR ACTUAL BUILDING
 CONSIDERING THE FACTS LISTED ON ITEM #1
 ABOVE. SEC. 104.2.1.2 CITY AMENDMENTS TO
 FBC 2001.
  
 3- PROVIDE COMPLETE INFORMATION ON SHEET
 17 AS REQUIRED BY GUIDE TO USE CHARTS
 AND GRAPHS ON SHEET 2 OF THE ROLL UP
 SHUTTER DRAWINGS.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.