Plan Review Notes
Plan Review Notes For Permit 05061737
Permit Number 05061737
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-21 00:00:00 
 PLEASE PROVIDE A PANEL DESIGNATION FOR
 THE CIRCUITS OF ORIGIN, BRANCH CIRCIUT
 NUMBERS AT THE POLES.
 ALSO PROVIDE LOAD CALCULATIONS FOR THE
 PANEL BEING USED INDICATING EXISTING AND
 PROPOSED LOADS.
  
 THE PERSON RESPONSIBLE FOR THE PLAN MUST
 PRINT NAME AND SIGN PLANS PER 104.2.1
 FBC. IF DESIGN PROFESSIONAL IS
 RESPONSIBLE SEE 471 OR 481 FS, WHICHEVER
 APPLIES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW