2005-07-15 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE PRIME MOVER FOR THE
 GENERATOR. HIGH LITE ON SPECS.
  
 2}INDICATE WHICH TRANSFER SWICH IS
 PROPOSED. 4 WERE SUBMITTED.
  
 3} GIVE THE SIZE OF ALL CONDUCTORS AND
 CONDUITS BEING INSTALLED. FROM THE
 GENERATOR IT IS NOT CLEAR WHERE THE
 CONDUIT TERMINATES. SEE SITE PLAN. ALSO
 SEE 445.13 FOR FEEDERS @115%
  
 4} THE DESIGNER OF RECORD MUST PRINT AND
 SIGN NAME ON PLANS PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
  