Plan Review Notes For Permit 05061729 |
Permit Number |
05061729 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-15 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} INDICATE THE PRIME MOVER FOR THE | | GENERATOR. HIGH LITE ON SPECS. | | | | 2}INDICATE WHICH TRANSFER SWICH IS | | PROPOSED. 4 WERE SUBMITTED. | | | | 3} GIVE THE SIZE OF ALL CONDUCTORS AND | | CONDUITS BEING INSTALLED. FROM THE | | GENERATOR IT IS NOT CLEAR WHERE THE | | CONDUIT TERMINATES. SEE SITE PLAN. ALSO | | SEE 445.13 FOR FEEDERS @115% | | | | 4} THE DESIGNER OF RECORD MUST PRINT AND | | SIGN NAME ON PLANS PER 104.2.1 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|